Gas Line Installation; Aeration Adjustment; Gas Pipe Pressure Testing - Regency FireGenie PG36D Owners & Installation

Table of Contents

Advertisement

PG36D-NG System Data
For 0 to 4500 feet altitude
Burner Inlet Orifi ce Sizes: #37( 2.65mm)
Max. Input Rating
33 Mj/h
Supply Pressure
min. 1.13 kPa
Manifold Pressure
(High)
1.0 kPa
Electrical: 240 V A.C. System.
Circulation Fan: variable speed 130 CFM.
Log Set: Ceramic fi bre, 7 per set.
Flue System: Simpson Dura-Vent Direct
Flue System or Regency
Flue System (Flex)
PG36D-LPG System Data
For 0 to 4500 feet altitude
Burner Inlet Orifi ce Sizes: #52 (1.61 mm)
Max. Input Rating
31 Mj/h
Supply Pressure
min. 2.75 kPa
Manifold Pressure
(High)
2.60 kPa
Electrical: 240 V A.C. System.
Circulation Fan: variable speed 130 CFM.
Log Set: Ceramic fi bre, 7 per set.
Flue System: Simpson Dura-Vent Co Axial
Flue System
®
Regency
PG36D Gas Log Fireplace
INSTALLATION
The gas line can be brought through either the
right or the left side of the appliance. The gas
valve is situated on the right hand side of the
unit and the gas inlet is on the right hand side
of the valve.
Note: If the gas line is being installed from
the left side, be sure to leave room to
accommodate servicing of the fan.
The gas line connection may be made of
rigid pipe, copper pipe or an approved fl ex
connector. (If you are using rigid pipe, ensure
®
Direct
that the valve can be removed for servicing.)
Since some municipalities have additional local
codes it is always best to consult with your local
authorities and the AS5601-2004 or NZS 5261
installation code.
When using copper or fl ex connectors use only
approved fi ttings. Always provide a union so
that gas lines can be easily disconnected for
servicing. Flare nuts for copper lines and fl ex
connectors are usually considered to meet this
requirement.
Important: Always check for gas leaks with a
soap and water solution or gas leak detector.
Do not use open fl ame for leak testing.
ADJUSTMENT
The air shutter can be adjusted by moving the
adjusting wire up or down. The wire is accessed
through the bottom louvre opening. Open the air
shutter for a blue fl ame or close for a yellower
fl ame. The burner aeration is factory set but
may need adjusting due to either the local gas
supply or altitude. This adjustment is performed
by the gas fi tter.
Minimum Air Shutter Opening:
5 mm
6.4 mm
CAUTION: Carbon will be produced if air shutter
is closed too much.
Note: Any damage due to carboning
resulting from improperly setting
the aeration controls is NOT covered
under warranty.
Closed - Tall yellow
Open - Short Blue
GAS LINE
AERATION
NG
LPG
INSTALLATION
GAS PIPE PRESSURE
TESTING
The appliance must be isolated from the gas
supply piping system by closing its individual
manual shut-off valve during any pressure
testing of the gas supply piping system at test
pressures equal to or less than 1/2 psig. (3.45
kPa). Disconnect piping from valve at pressures
over 3.45 kPa (14" w.c.).
The manifold pressure is controlled by a regulator
built into the gas control, and should be checked
at the pressure test point.
Note:
To properly check gas pressure,
both inlet and manifold pressures
should be checked using the valve
pressure ports on the valve.
1) Make sure the valve is in the "OFF"
position.
2) Loosen the "IN" (# 3) and/or "OUT" (# 4)
pressure tap(s), turning counterclockwise
with a 1/8" wide fl at screwdriver.
3) Attach manometer to "IN" and/or "OUT"
pressure tap(s) using a 5/16" (8mm) ID
hose.
4) Seal and or check the pilot outlet (# 8)
5) The pressure check should be carried out
with the unit burning and the setting should
be within the limits specifi ed on the safety
label.
6) When fi nished reading manometer, turn
off the gas valve, disconnect the hose and
tighten the screw (clockwise) with a 1/8" fl at
screwdriver. Screw should be snug, but do
not over tighten.
21

Advertisement

Table of Contents
loading

Table of Contents