Owners & Installation Zero Clearance Room Sealed Gas Fireplace See Thru PG121-NG PG121-LPG Left Corner PG121LC-NG PG121LC-LPG Right Corner PG121RC-NG PG121RC-LPG Pier PG131-NG PG131-LPG PLEASE KEEP THESE INSTRUCTIONS FOR FUTURE REFERENCE Your unit should be serviced annually by an authorised service...
Page 2
Association for both safety and efficiency. As it also bears our own mark, it promises to provide you with economy, comfort and security for many trouble free years to follow. Please take a moment now to acquaint yourself with these instructions and the many features of your Regency Fireplace. IMPORTANT: If the unit is to be installed into a bathroom, optional Neo ceramic glass Part# 360-946 Front or Part# 360-948 Side must be purchased and installed in place of the tempered glass supplied with the unit.
TABLE OF CONTENTS Safety Label ............... 4 Operating Instructions ..........29 Lighting Procedure ............ 29 Shutdown Procedure ..........29 First Fire ..............29 Important Message ............ 5 Normal Operating Sounds of Before You Start ............5 Gas Appliances ..........29 General Safety Information .........
INSTALLATION IMPORTANT: SAVE THESE INSTRUCTIONS GENERAL SAFETY INFORMATION INSTALLATION CHECKLIST Note: These units are non-load bearing. BEFORE YOU START CAUTION: Any alteration to the product that causes sooting or carboning that results in damage is not the responsi- bility of the manufacturer.
INSTALLATION LOCATING YOUR GAS FIREPLACE A) PG121 - See Thru B) PG131 - Pier C) PG121LC - Left Corner Note: For Exterior Flue Termination Locations see page 12. D) PG121RC - Right Corner...
INSTALLATION CLEARANCES Clearance to Combustibles from: Back Side Floor CAUTION REQUIREMENTS: The top, back and sides of the fireplace are defined by standoffs. The metal ends of the standoffs may NOT be recessed into combus- tible construction. Determine the total thickness of the finished floor (eg. tile, carpet, slate) to allow the finished surface to be flush with the base of the unit.
INSTALLATION FRAMING AND FINISHING PG121 (See Thru) PG131 (Pier) PG121LC / PG121RC (Corner Unit) CAUTION: Verify your fireplace dimensions, framing methods and finished wall facing details before framing. Determine the total thickness of facing material - drywall plus ceramic tiles, slate, etc.
INSTALLATION FACING & FINISHING REQUIREMENTS FLUEING UNIT ASSEMBLY INTRODUCTION PRIOR TO INSTALLATION Note: These flue pipes must not be con- nected to any other appliance.
Page 13
FLUEING ARRANGEMENT - HORIZONTAL TERMINATIONS Regency Direct Vent System (Flex) Horizontal Terminations Only Regency Direct Vent (Flex) System Termination Kit (Part# 946-513) includes all the parts needed to install the PG121/PG121LC/ PG121RC/PG131 with a maximum run of 2 feet. 5) AstroCap Notes: 1) Liner sections should be continuous without any joints or seams.
The Regency AstroCap is certified for installations using FPI venting systems as well as Simpson Dura-Vent® and Direct Vent GS. Regency , and Regency AstroCap are the proprietary trade- marks of FPI Fireplace Products International Ltd. Simpson Dura-Vent Dura-Vent® and Direct Vent GS are registered and/or propri- etary trademarks of Simpson Dura-Vent Co.
INSTALLATION FLUEING ARRANGEMENTS - HORIZONTAL TERMINATIONS SIMPSON DURA-VENT DIRECT VENT GS SYSTEM (LPG & NG) Note: 1) A maximum of three 90 elbows are permitted. Simpson Dura-Vent 2) Minimum distance between elbows is 1 ft. (305mm). 4" inner diameter 6-5/8" outer diameter ...
Page 16
INSTALLATION 2' (610mm) Min. 1' (305mm) Max. 3' (914mm) Max. 1' (305mm) Minimum 2' (610mm) Maximum 3' (914mm) Min. 3' (914mm) Max. 6' (1.86m) Max. 2' (610mm) Minimum 5' (1.5m) Maximum 4' (1.22mm) Min. 5' (1.5m) Max. 9' (2.7m) Max. 3' (914mm) Minimum 8' (2.4m) Maximum 5' (1.5m) Min.
Page 17
INSTALLATION FLUEING ARRANGEMENTS - VERTICAL TERMINATIONS SIMPSON DURA-VENT DIRECT VENT GS SYSTEM (LPG & NG) Flue must be supported at offsets Maintain clearances to combustibles as listed on page 9. Firestops are required at each floor level and whenever passing through a wall. ...
Page 18
INSTALLATION 1' (305mm) Minimum 2' (610mm) Maximum 1' (305mm) Minimum 4' (1.22m) Maximum 2' (610mm) Minimum 4' (1.22m) Maximum 2' (610mm) Minimum 6' (1.86m) Maximum 3' (914mm) Minimum 6' (1.86m) Maximum 3' (914mm) Minimum 9' (2.7m) Maximum 4' (1.22m) Minimum 8' (2.4m) Maximum 4' (1.22m) Minimum 12' (3.6m) Maximum...
Page 19
INSTALLATION 2' (610mm) Minimum 3' (914mm) Maximum 3' (914mm) Minimum 6' (1.86m) Maximum 4' (1.22m) Minimum 9' (2.7m) Maximum 5' (1.5m) Minimum 12' (3.6m) Maximum Please note minimum 1 foot between 90 elbows is required. Diagram 12 HORIZONTAL INSTALLATIONS Install the flue system according to the manufacturer's instructions included with the components.
INSTALLATION VERTICAL TERMINATION Diagram 3 to ensure that the termination is not recessed into the siding. Diagram 1 Diagram 4: The upper half of the flashing is installed under the roofing material and not nailed down until the chimney is installed. This allows for small adjustments.
INSTALLATION The liners must slip over the collars a minimum of 1-3/8". Note: To make the installation more aesthetically pleas- ing, recom- mend framing out a square to mount the terminal to. be used to ensure that the termi- nation is not recessed into the siding.
Page 22
INSTALLATION Conversion Kit for NG to LPG Model #736-969 Front Cover brick panel is very fragile - handle with care. Pilot Pilot Pilot Pilot Tube Extrusion Orifice Assembly Tube 5 Pin Molex Connector Diagram 1: Remove the left and right screws and then slide the burner assembly away from the orifice and lift out.
Page 23
INSTALLATION Minimum pressure: NOTE: Cable Jumper Location Electric Modulator Jumper WARNING: Adjusting the Outlet Pressure Maximum pressure: NOTE:...
Burner Inlet Orifice Sizes: Note: If you have an incorrect flame pat- Pilot Orifice LPG tern, contact your Regency dealer for further instructions. Max. Input Rating Min. Input Rating Incorrect flame pattern will have small,...
INSTALLATION LOG INSTALLATION do not force into position. Read the instructions below carefully and refer to the diagrams. If logs are broken do not use the unit until they are replaced. Broken logs can interfere with the pilot operation. Please note that there are 2 of each log. This log set is mirrored front and back.
Page 26
INSTALLATION Caution: Do NOT cover burner ports. Grate Post Place Log 329 onto pin. Grate Post...
INSTALLATION GLASS DOOR FINISHING TRIM LOUVERS & GRILLS REMOVAL NOTE: Do not tighten the screw entirely, ensure that some room is left to be able to hang the grill or louver over the screw. Slide Trim into slot. Push trim tight against magnet.
OPERATING INSTRUCTIONS AERATION FIRST FIRE NORMAL OPERATING ADJUSTMENT SOUNDS OF GAS APPLIANCES 10mm open 10mm open normal operating sounds NOTE: This adjustment is only to be made by an authorised person. Blower: Note: When the glass is cold and the appliance is lit, it may cause con- densation and fog the glass.
OPERATING INSTRUCTIONS COPY OF THE LIGHTING PLATE INSTRUCTIONS MAINTENANCE INSTRUCTIONS A ) BEFORE LIGHTING smell all around the appliance B) Do not use this appliance if any part has been area for gas. Be sure to smell next to the floor under water.
MAINTENANCE DOOR GLASS VALVE TRAY REMOVAL LOG REPLACEMENT Note: Improper positioning of logs may create carbon build-up and will The brick panels are very fragile severely alter the unit's perform- - handle with care. ance which is not covered under warranty.
Page 33
MAINTENANCE 5 Pin Molex Connector Remove Left & Right Side Base Brick Panels Igniter and 5 Pin Molex Flame Cables Connector from the Valve. Remove the 2 Long Base Brick Panels...
PARTS LIST ELECTRONIC COMPONENTS PARTS LIST 910-915 910-082 910-089 910-088 910-912 910-084 910-526 910-080 910-906 910-083 910-514 910-521, 910-522, 910-523 910-916 Fan Resistor Intermittent Pilot Direct Spark Ignitor Flame Cable Spark Cable Control Box Manual Control Valve Control Box Cable N/A* Control Box Cable Control Box Cable...
Page 35
PARTS LIST PG121 (SEE THRU) MAIN ASSEMBLY Part # Description Part # Description Part # Description...
Page 36
PARTS LIST PG131 (PIER) MAIN ASSEMBLY Part # Description Part # Description Part # Description...
Page 37
PARTS LIST PG121RC (RIGHT CORNER) MAIN ASSEMBLY Part # Description Part # Description Part # Description...
Page 38
PARTS LIST PG121LC (LEFT CORNER) MAIN ASSEMBLY Part # Description Part # Description Part # Description...
Page 39
PARTS LIST PG121/PG121LC/PG121RC/PG131 BURNER ASSEMBLY & LOG SET Part # Description...
Electrical components such as fans, switches, wiring, product. thermodiscs, remote control, thermopiles, thermocouples Regency Industries Ltd., shall in no event be liable for any and gas valves are covered for one year from the date of special, indirect consequential damages of any nature purchase.