Galvin Specialised Safe-Cell TZ-FLOWTPANMDT Product Installation Manualline page 5

Ducted dual flush pan assembly for mains with controller

Advertisement

3.
Connect water
It is recommended that the cold water inlet is
a minimum DN25 and has a minimum flow
rate of 1.5 liters/second.
Connect the water supply to the strainers and
turn on water supply. Check for leaks.
Adaptors/Reducer supplied by the installer
must be in accordance with AS/NZS 3500.
Do not apply heat near this product. Heat
generated by soldering could damage
plastic, nylon, or electrical parts and seals
and will void the warranty.
Version 1, 18 December 2020, Page 5 of 12
Note: Controller must be mounted away from any
moisture or potential water splashing.
4. Mount control module
Attach the control module to a flat surface away
from any possible splashing or moisture using
supplied Velcro.
Find a suitable place to mount the control module
within 5mtrs of the service and 3mtrs of the GPO.
All electrical components should be protected
from contact with water or excessive heat and
installed in accordance with local regulations.
Flowmatic Control Module is programmed as per
standard settings for a mains flushing system.