Installation - Galvin Specialised Safe-Cell TZ-FLOWTPANMDT Product Installation Manualline

Ducted dual flush pan assembly for mains with controller

Advertisement

INSTALLATION

Avoid common installation errors :
-
Incorrect supply pipe size installed.
-
Non-compliance to Australian Standards.
-
Water pressure not tested before installation
-
Plastic Pipe (In many brands of plastic pipe and
associated fittings the internal diameter is not
equivalent to copper).
1. Mount face plate
The stainless steel face plate is always
mounted flush to the wall.
Mount faceplate to the wall using the back
plate and nyloc nuts (Do not over tighten
max.35 Nm).
Cut the studs to suit if required.
Ensure button leads are pushed through the
centre hole in back plate before tightening the
nyloc nuts and apply a thin bead of silicon on
the edge of the wall cut out.
If extension leads are required, please
contact Galvin Engineering.
Do not force the faceplate to fit onto wall or
attempt to dissamble components, as this
could result in damage to sensor push
button.
Version 1, 18 December 2020, Page 4 of 12
-
Lines not flushed before installation.
-
No access for service.
Valve not commissioned properly.
-
2.
Connect solenoid
50mm flush pipe and adapter must be supplied
by installer.
Connect solenoid assemblies into the outlet
panpipe at a minimum height of 450mm above
the top rim of the pan.
Ensure that the solenoid is installed in the
correct direction (the arrow on the solenoid body
must align with the direction of water flow).
Line strainers are supplied attached to the solenoid
valves. Removal of these strainers may void the
warranty.
Ensure no thread tape, copper swarf, sand or
other debris enters and fouls the solenoid
valve.
Make sure solenoid valve is orientated such that
the electrical wiring is not twisted and connectors
are easily accessible.