Checking Grid Monitoring Parameters; Removing The Sd Card - Viessmann Vitovalor PT2 Installation And Service Instructions For Contractors

Fuel cell based micro chp unit with integral gas condensing boiler and adjacent cylinder module natural gas version
Table of Contents

Advertisement

Fuel cell module
(cont.)

Checking grid monitoring parameters

A
GEN
MNT
ITEM
ERR
GRD
DCT
Fig. 81
ITEM
Meaning
81
AC undervoltage stage
83
AC overvoltage stage 1
84
AC overvoltage stage 2
85
Frequency drop stage 1
86
Frequency drop stage 2
87
Frequency rise
8a
Islanding operation
8b
Nominal voltage
8c
Nominal current

Removing the SD card

The SD card is delivered already in place. Data stor-
age for the fuel cell module begins as soon the
Vitovalor PT2 is commissioned.
STATE
SET
B
Set value
184 V
262.2 V
237.7 V
47.5 Hz
47 Hz
52 Hz
1.0 Hz/s
230 V
3.26 A
Diagnosis and service checks
1. Remove cover
.
A
2. On programming unit
the required display (81 to 8c).
In displays 81 to 8c, the set value and the
response time are shown alternately.
For an explanation of the displays: See the follow-
ing table.
Note
The Vitovalor has grid and system protection integra-
ted in the fuel cell module. The specified response
times consist of the settings for the protection relay
and the disconnection time of the coupling switch.
Response time
2.5 s
1.0 s
0.5 s
20.0 s
0.5 s
0.5 s
0.0 s
, use
in ITEM to select
B
111