Checking Outputs (Actuator And Sensor Test) - Viessmann Vitovalor PT2 Installation And Service Instructions For Contractors

Fuel cell based micro chp unit with integral gas condensing boiler and adjacent cylinder module natural gas version
Table of Contents

Advertisement

Diagnosis and service checks
Gas condensing module
5. "Message history"
The following is displayed in the message lists:
Date and time of the occurrence of the notifica-
tion
Notification number
Description of the notification
Subscriber number of the component on which
the message has occurred:
PlusBus subscriber components
0
EM-S1 extension (ADIO electronics
module)
1 - 15
EM-M1, EM-MX and EM-P1 extensions
(ADIO electronics module)
17 - 31 EM-EA1 extension (DIO electronics
module)
32 - 47 Cylinder module, EM-M2, EM-S2 exten-
sions (M2IO electronics module)
49 - 63 Vitotrol 200-E
64
SDIO/SM1A electronics module
CAN BUS subscriber components
1
HMU heat management unit
50 BCU burner control unit
58 RF module (wireless module)
59 HMI programming unit
60 Fan unit
90 Gateway
Low power radio subscriber components
48 - 63 Vitotrol 300-E

Checking outputs (actuator and sensor test)

Note
When the actuator and sensor test is started, all actua-
tors are initially disabled or valves moved to their cen-
tral position.
Tap the following buttons:
01. "
"
02. "Service"
03. Enter password "viservice".
04. Use
to confirm.
05. "Actuator and sensor test"
108
(cont.)
6.
7. If you wish to delete the messages, tap .
8.
06.
07. Use
08. Tap the required actuator function. Several func-
09. If necessary, tap
10. Use
"Faults" to call up saved fault messages. For
further details, see the following chapter "Fault
messages".
"Service messages" to call up saved service
messages.
P.1 Interval until the next service.
P.4 Top up heating water.
P.8 Interval in burner hours until the next serv-
ice.
"Status", to call up the saved status messages.
S.60 Summer mode active (exterior temperature
savings function)
S.75 DHW circulation pump active
"Warnings" to call up saved warning messages.
A.12 Real time clock battery flat.
Measure: Replace the battery
(type CR2032) in the HMU heat manage-
ment unit.
A.18 Possible condensate backup in the heat
cell
Measure: Check the combustion chamber
and condensation drain.
A.20 Service interval could not be activated.
Measure: Check the time and date set-
tings.
"Information", to call up saved service informa-
tion.
I.55 Maximum DHW temperature reached
I.56 External demand active
I.57 External blocking active
I.59 Parameters have been restored (parameter
set was flashed to BCU electronics mod-
ule).
to confirm
to confirm the security prompt.
Note
If an actuator function is not possible due to the
running process, the function is interrupted. A
message appears.
/
to select the required group. See the
table below.
tions can be activated simultaneously.
to confirm. The functions are
active for 30 s.
to terminate the Actuator and sensor test.