Xylem Bell & Gossett e-82SC Instruction Manual page 12

Hide thumbs Also See for Bell & Gossett e-82SC:
Table of Contents

Advertisement

3 Product Description
Table notes
1. An external flush is required on low pressure systems that contain a high concentration
of abrasives.
2. For operating temperatures above 250°F, a cooled flush is required and is
recommended for temperatures above 225°F for optimum seal life. On closed
systems, cooling is accomplished by inserting a small heat exchanger in the flush line
to cool the seal flushing fluid.
3. Flush-line filters and sediment separators are available on request.
10
Series e-82 INSTRUCTION MANUAL

Advertisement

Table of Contents
loading

This manual is also suitable for:

Bell & gossett e-82Bell & gossett e-82 series

Table of Contents