3. The Fire Bell is Continuous option is disabled (section [014]:
[8])
4. The Transmission Delay is disabled, if Transmission Delay
is not required (section [370])
Fire Troubles are not supported in Walk Test.
To perform a Walk Test, do the following:
Step 1 - Enter Installer Programming
Step 2 - Enter Section [901]
When any zone is violated the panel will activate the Bell Output
for two seconds, log the event to the Event Buffer and
communicate the alarm to central station. Each zone should be
tested several times during the test. Check the event buffer to
ensure that all zones and FAP keys are functioning properly.
R
A
M
D
E
S
C
To stop the test, you must do the following:
Step 1 - Enter Installer Programming
Step 2 - Enter Section [901]
Check the Event Buffer after the Walk Test is complete, to
ensure that the Audible/Silent 24-hr PGM alarms have been
restored.
\
The Alarm Memory is cleared upon entering Walk
Test mode. When the Walk Test is complete, the
Alarm Memory light will remain lit, but there will
be no alarms in memory. The light will turn off the
next time the panel is armed.