Telephone Line Monitor (Tlm); Siren; Test Transmission - DSC PC5008 Installation Manual

Hide thumbs Also See for PC5008:
Table of Contents

Advertisement

P
R
O
G
[24] Audible 24 Hour (PGM2 Only)
A Panic button may be placed on the PGM2 Terminal for use as
an Audible 24 Hour Panic. When the button is pressed, LCD
keypads will indicate "System in Alarm", the bell will sound until
the Bell Cut-off expires or until a valid access code is entered,
and the PGM2 Alarm reporting code will be sent to the central
station. PGM output option [24] will not activate other
programmable outputs except for outputs programmed as [01].
This input does not follow Swinger Shutdown.
PGM Output Attributes
In addition to programming the output type, you must also
program the PGM output attributes for each output.
PGM output options [09] "System Trouble" and [10] "System
Event" have their own unique set of attributes listed below the
description of each output type.
PGM output options [01], [03], [05]-[08], [11]-[24] have the
following attributes:
Attribute
ON
[1] ........... Output Enabled
[3] ........... True Output
Attribute ON: the output energizes when activated
Attribute OFF: the output de-energizes when
activated
[4] ........... Output Pulsed
Attribute ON: the output will activate once for the
amount of time programmed in section [164]
when initiated by the user
Attribute OFF: the output will turn ON and OFF
when initiated by the user.
(only applicable to options [19]-[22])
[5] ........... Access Code Req.
Attribute ON: the output requires a code for
activation.
Attribute OFF: no code required.
(only applicable to keypad-activated outputs)
PGM attributes return to their default settings when you change
PGM output options. Please see the programming worksheets
for a list of the default settings for each PGM output type.
Care should be taken in selecting the normal and active states
of each PGM output to ensure that an undesirable output state
does not occur after a loss and restore of AC power.
Attribute [3] must be ON (default) for PGM output
options [16], [23] and [24].
If you program more than one PGM output as the
same output type (eg. if PGM1 and PGM2 are both
programmed as [19] Command Output 1), the
settings for output attributes [1], [2] and [5] must
be the same. This does not apply to outputs
programmed as types [09] and [10].
○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○
PGM Output Attributes ............................ Section [141]-[142]
○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○

5.12 Telephone Line Monitor (TLM)

When the TLM Enable option is selected, the panel will supervise
the telephone line and will indicate a trouble condition if the
telephone line is disconnected.
If the TLM Enable option is ON, the panel will check the
telephone line every 10 seconds. If the telephone line voltage
R
A
M
OFF
Disabled
Inverted Output
Output ON/OFF
No code Req.
D
E
S
C
is below 3V for the number of checks programmed in the TLM
Trouble Delay section, the panel will report a TLM trouble. The
default number of checks is 3. Enter a number from [003] to
[255] in the TLM Trouble Delay section to change the number
of checks before the TLM trouble is reported. Programming a
delay means that a momentary interruption of the telephone line
will not cause a trouble condition.
If the TLM Trouble Beeps When Armed option is enabled, the
panel will indicate a TLM trouble at the keypad while the system
is armed. To activate the bell output in the case of a TLM trouble
while the system is armed, the TLM Audible (Bell) When
Armed option must be selected.
When the trouble condition is restored, the panel can send a
TLM Restoral reporting code. Any events which occur while
the telephone line is down will also be communicated.
If the LINKS 1000 Cellular Communicator, or LINKS2X50 is
being used, the panel can be programmed to report a TLM
Trouble Reporting Code.
○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○
TLM Enable/Disable ................................... Section [015]: [7]
TLM Trouble Beeps When Armed or
TLM Audible (Bell) When Armed ............... Section [015]: [8]
TLM Trouble Reporting Code ............................ Section [349]
TLM Restoral Reporting Code .......................... Section [350]
TLM Trouble Delay ............................................ Section [370]
○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○

5.13 Siren

The siren will silence after the number of minutes programmed
for the Bell Cut-off time have passed.
The panel supervises the Bell output. If an open condition is
detected, the panel will immediately indicate a trouble condition
by beeping the keypad twice every 10 seconds to alert the
owner of the problem. The panel can send a Bell Circuit
Trouble and Trouble Restoral reporting codes to indicate the
situation (see Section 5.8 "Communicator – Reporting Codes").
If the Temporal Three Fire Signal option is enabled, all Fire
signals will follow the Temporal Three Pattern as described in
NFPA 72. If turned OFF all Fire signals will sound a one second
on, one second off cadence.
If Fire Bell Continuous is enabled, the alarm output will sound
until a code is entered. If disabled, the alarm will sound until a
code is entered or the bell cut-off time has expired.
○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○
Bell Cut-off ......................................................... Section [005]
Bell Circuit Trouble Reporting Code ................. Section [349]
Bell Circuit Trouble Restoral Reporting Code .. Section [350]
Temporal Three Fire Signal Enable/Disable . Section [013]: [8]
Fire Bell Continuous ................................... Section [014]: [8]
○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○

5.14 Test Transmission

To ensure that the communication link with the central station is
functioning properly, the panel can be programmed to send a
test transmission signal on a regular basis.
The panel can send a Periodic Test Transmission Reporting
Code at the programmed Test Transmission Time of Day. The
Test Transmission Cycle determines the period of time between
tests. The option Land Line Test Transmission in Minutes/
Days allows you to select whether the Land Line Test
Transmission cycle will be counted in minutes or days. If you
have selected the test transmission cycle to be in minutes, the
Test Transmission Time of Day counter will not apply.
23
R
I
P
T
I
O
N
S

Advertisement

Table of Contents
loading

This manual is also suitable for:

Power608

Table of Contents