Zone Attributes - DSC PC5008 Installation Manual

Hide thumbs Also See for PC5008:
Table of Contents

Advertisement

P
R
O
G
A violated Fire zone will be displayed on all keypads and can
be delayed at any keypad. Typically this zone is used for
latching smoke detectors.
[08] Standard 24 Hour Fire Zone
Do not wire Fire zones on keypad zone terminals
if the DEOL supervision option is enabled for the
panel (section [013], option [2]).
When this zone is violated, the panel will immediately latch the
alarm output and communicate to the central station. The alarm
will sound until the Bell Cutoff time expires (Section [005]
"System Times"), or until a code is entered (see Section 5.13
"Siren").
A violated Fire zone will be displayed on all keypads. Typically
this zone is used for pull stations.
[09] 24 Hour Supervisory Zone
If this zone is violated when the system is either armed or
disarmed, the panel will report to the central station, and will log
the zone alarm to the Event Buffer. This zone gives a silent alarm
by default.
Do not wire 24-Hour Supervisory zones on
keypad zone terminals.
[10] 24 Hour Supervisory Buzzer Zone
If this zone is violated when the system is either armed or
disarmed, the panel will immediately latch the keypad buzzer
until a valid access code is entered and will immediately
communicate to the central station.
[11] 24 Hour Burglary Zone
If this zone is violated when the system is either armed or
disarmed, the panel will immediately latch the alarm output and
communicate to the central station. The alarm will sound until
the Bell Cutoff time expires (Section [005] "System Times"), or
until a code is entered (see Section 5.13 "Siren").
[12] - [20]
The following zone definitions operate similar to the 24 Hour
Burglary except for the System Event output type and the SIA
identifier:
[12] 24 Hour Holdup Zone - This zone gives a silent alarm by
default.
[13] 24 Hour Gas Zone
[14] 24 Hour Heat Zone
[15] 24 Hour Medical Zone
[16] 24 Hour Panic Zone
[17] 24 Hour Non-Medical Emergency Zone
[18] 24 Hour Sprinkler Zone
[19] 24 Hour Water Flow Zone
[20] 24 Hour Freezer Zone
[21] 24 Hour Latching Tamper
If this zone is violated, the installer must enter Installer's
Programming before the system can be armed.
Wireless zones should not be programmed as
zone types [22] - [24].
[22] Momentary Keyswitch Arm Zone
Momentary violation of this zone will alternately arm/disarm the
system.
[23] Maintained Keyswitch Arm Zone
When this zone is violated, the system will arm. When this zone
is secured, the system will disarm.
R
A
M
D
E
S
C
[24] LINKS Answer Zone
Downloading can be performed via the LINKS1000 Cellular
Communicator (if used) when the conventional telephone line is
disconnected. If this operation is desired, connect the RING
terminal of the LINKS1000 to a LINKS Answer zone (see Section
2.11 "LINKS Zone Wiring"). Refer to the LINKS 1000 Installation
Manual for more information.
Do not wire LINKS Answer zones on keypad zone
terminals.
[25] Interior Delay Zone
This zone type is normally used with motion detectors and has
a standard exit delay time.
If the panel is Away armed (a delay zone is violated during the
exit delay, or the Away function key is used), the Interior Delay
zone will work the same as the Interior zone [04].
If the panel is Stay armed (a delay zone is NOT violated during
the exit delay, the Stay key is used, or [ ][9] is used for arming),
a violation of the zone will initiate Entry Delay 1.
[87] Delayed 24 Hour Fire (Wireless)
This zone type operates the same as [07] Delayed 24 Hour Fire
Zone and must be used if the smoke detector is wireless.
[88] Standard 24 Hour Fire (Wireless)
This zone type operates the same as [08] Standard 24 Hour Fire
Zone and must be used if the smoke detector is wireless.
○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○
Zone Definitions ............................................................. [001]
Zone Assignments ......................................................... [202]
○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○
5.3

Zone Attributes

All zones, with the exception of 24 Hour and Fire,
will provide an exit delay.
Attributes for Fire Zones should never be
changed from the default settings.
Additional zone attributes can be programmed to customize
the operation of a zone for a specific application. The following
attributes are programmable for each zone:
• Audible / Silent – This attribute determines whether or not the
zone will activate the alarm output.
• Pulsed / Steady – This attribute determines whether the alarm
output will be steady or will pulse on and off every second.
• Activate Chime – This attribute determines whether or not
the zone will activate the chime feature (see Section 3.4 – "[ ]
[4] Door Chime On/Off").
• Bypass Enable – This attribute determines whether or not the
zone can be manually bypassed (see Section 3.4 – "[ ] [1]
Bypassing and Reactivating Stay/Away Zones").
• Force Arm Enable – This attribute determines whether or not
the system can be armed while a zone is violated. At the end
of the exit delay, if this type of zone is violated, it will be
ignored by the panel. Once the zone is secured, it will be
monitored by the system. This zone attribute, for example,
will allow the user to arm the system with the garage door
open. Later, when the door is closed, it will be armed along
with the rest of the system. Do not program this attribute for
24Hr zones.
• Swinger Shutdown Enable – This attribute determines
whether or not the panel will shut down the communicator and
bell for a zone once its swinger limit has been reached (see
Section 5.19 "Swinger Shutdown")
16
R
I
P
T
I
O
N
S

Advertisement

Table of Contents
loading

This manual is also suitable for:

Power608

Table of Contents