RH% Sensor
Calibration
Differential
temperature
adjustment
Deadband setting
Test mode setting
System Selection
48
Setting 16
This setting will allow the adjustment of RH% reading
by +/-10%. Factory default is 0%RH.
Setting 17
•
•
This setting changes the system/compressor; turn on
temperature above setpoint. Factory default is set to 1
Deg F.
Example: Sensor reading = 55 Deg F (13 Deg C)
Setting 17 Set to +3 Deg F
System/compressor turns on at 58 Deg F. (14 Deg C)
Setting 18
•
•
This setting is the minimal allowable temperature
difference between heating and cooling setpoints.
Maximum is 5 Deg F (-15 Deg C), minimum is 1 Deg
F. (-17 Deg C) Factory default is set to 2 Deg F (-16
Deg C)
Setting 19
•
•
Setting 20
• DO NOT CHANGE
Press "Settings" button to advance to Setting 17
Press the "Up" or "Down" buttons to adjust to the
desired setpoint.
Press "Settings" button to advance to Setting 18.
Press the "Up" or "Down" buttons to adjust to the
desired setpoint.
Press "Settings" button to advance to Setting 19.
Press the "Up" or "Down" buttons to adjust to the
desired setpoint. When set to one the controller
will automatically turn on all outputs with the
exception of electric heat. Factory default is zero.
Zero (0) = Off.
One (1) = On