Wine Guardian D050V Installation, Operation And Maintenance Manual page 46

Ducted and ducted vertical wine cellar cooling systems
Table of Contents

Advertisement

Advanced Settings--
Compressor anti-
short cycling time
Set up remote sensor
or thermostat
Enable or disable
defrost sensor input
46
Setting 8
• Press "Settings" button to advance to Setting
8.
• Press the "up" or "down" arrow buttons to
adjust number to the access code 12. Press
"Settings" button to continue onto Setting 9
through 19.
Setting 9
• Press "Settings" button to advance to Setting
9.
• Press the "Up" or "Down" arrow buttons to
adjust to the desired time in one-minute
increments. Maximum is 10 minutes,
minimum is 0 minutes.
Compressor anti-short cycling time is the
amount of allowable time between compressor
stop and restart. Rapid start/stop of compressors
can cause premature failure. Factory default is 5
minutes.
WINE GUARDIAN DOES NOT
RECOMMEND SETTINGS LOWER THAN
FACTORY DEFAULT.
Setting 10
• Press "Settings" button to advance to Setting
10.
• Press the "Up" or "Down" arrow buttons to
adjust to the desired setting.
rS = Remote sensor
rI = Remote interface
LI= Local interface – Through-the-wall unit
only
A = Averaging – Jumper position within
sensors must be adjusted. This will average
ALL Wine Guardian devises plugged into the
system. See page 42.
Setting 11
• Press "Settings" button to advance to Setting
11.
• Press the "Up" or "Down" arrow buttons to
adjust to the desired setpoint
• 1 will equal enabled and a 0 (zero) will equal
disabled.