NTI Triton VS80 Assembly, Installation And Operation Instructions page 12

Oil boiler
Table of Contents

Advertisement

Triton
Installation and Operation Instructions - Natural Draft
Table 5-1 Minimum Chimney Sizes
Minimum
Model
Breaching
Rectangular
Diameter
VS80
VS90
VS100
5 "
VS120
VS130
Notes:
1
6-3/4" x 6-3/4" inside liner.
2
Excessive breeching length or too many elbows and/or tee will cause restriction.
Draft Regulator
Secure breeching using
minimum of two screws,
equally spaced.
12
Minimum I=B=R Chimney
Round
1
6 "
8 " x 8 "
Figure 5-1 Breeching & Blocked Vent Switch
Minimum
Boiler Flue
Chimney
Collar Size
Height
15 '
6 "
Blocked Vent Switch
Blocked Vent Switch
Install the switch 6-8" above the boiler
breeching, refer to instructions included
with kit (mandatory in Canada).
VS80-130