Parameter Setting - Siemens SIMATIC S7-1500/ET 200МР Manual

Technology module tm count 2x24v (6es7550-1aa01-0ab0)
Hide thumbs Also See for SIMATIC S7-1500/ET 200МР:
Table of Contents

Advertisement

Configuring/address space
4.3 Manual operation (without technology object)
4.3.3

Parameter setting

You specify the properties of the technology module using various parameters. Depending on
the settings, not all parameters are available. When parameters are assigned in the user
program, the parameters are transferred to the module with the "WRREC" instruction and
data record 128 (Page 87).
You set the parameters of the module as follows in this operating mode:
Parameter setting using...
Hardware configuration in STEP 7
(TIA Portal)
Hardware configuration with GSD
file for distributed operation on
PROFINET IO
Hardware configuration with GSD
file for distributed operation on
PROFIBUS DP
Note
The "Operating with "Counting and measurement" technology object" and "Manual operation
(without technology object)" operating modes apply to one channel in each case. As a result,
you can also use a module with both operating modes.
40
Basic procedure
1. Insert the module from the hardware catalog under "Technology modules".
2. Set the device configuration and the parameters of the module in the hardware
configuration.
"Manual operation (without technology object)" must be set as the operating mode.
3. Download the project to the CPU.
1. Install the current PROFINET GSD file.
You will then find the module in the hardware catalog under "Other field devices >
PROFINET IO > I/O".
2. Set the parameters in the hardware configuration.
You can find information on the respective dependencies of the parameters in
function manual Counting, Measurement and Position Detection
(http://support.automation.siemens.com/WW/view/en/59709820).
3. Download the project to the CPU.
1. Install the current PROFIBUS GSD file.
You will then find the module in the hardware catalog under "Other field devices >
PROFIBUS DP > I/O".
2. Set the parameters in the hardware configuration.
You can find information on the respective dependencies of the parameters in
function manual Counting, Measurement and Position Detection
(http://support.automation.siemens.com/WW/view/en/59709820). The parameters
marked with
in the following tables are not configurable in the PROFIBUS GSD file.
1
3. Download the project to the CPU.
The parameters marked with
default setting.
4. If necessary, set the parameters marked with
ord 128.
in the following tables are downloaded with their
1
in the user program using data rec-
1
Technology module TM Count 2x24V (6ES7550-1AA01-0AB0)
Equipment Manual, 12/2020, A5E31870371-AC