Siemens SIMATIC S7-1500/ET 200МР Manual page 93

Technology module tm count 2x24v (6es7550-1aa01-0ab0)
Hide thumbs Also See for SIMATIC S7-1500/ET 200МР:
Table of Contents

Advertisement

Parameter data record
B.1 Parameter assignment and structure of parameter data record
Bit →
Bit 7
Byte ↓
4...51
52...99
4/52
4/52
Reserved
2)
5/53
5/53
Reserved
2)
6...7/
54...55
6/54
Sensor type:
00
: Sourcing output
B
01
: Sinking output
B
10
: Push-pull (sinking and
B
sourcing output)
11
: Invalid
B
7/55
Reaction to signal N:
00
: No reaction to sig-
B
nal N
01
: Synchronization at
B
signal N
10 to 11
: Invalid
B
92
Bit 6
Bit 5
Counter inputs (parameters for incremental encoders and pulse encoders)
Signal evaluation:
00
: Single
B
01
: Double
B
10
: Quadruple
B
11
: Invalid
B
Invert direc-
Enable
tion
diagnostic
1
interrupt on
wire break
Bit 4
Bit 3
Counter channel 0
Counter channel 1
Operating mode
Operating mode:
0000
: Invalid
B
0001
: Counting
B
0010 to 1111
: Invalid
B
Basic parameters
Enable
additional
diagnostic
interrupts
Signal type:
0000
: Pulse (A)
B
0001
: Pulse (A) and direction (B)
B
0010
: Count up (A), count down (B)
B
0011
: Incremental encoder (A, B phase-shifted)
B
0100
: Incremental encoder (A, B, N)
B
0101 to 1111
: Invalid
B
Filter frequency
0000
: 100 Hz
B
0001
: 200 Hz
B
1
0010
: 500 Hz
B
0011
: 1 kHz
B
0100
: 2 kHz
B
0101
: 5 kHz
B
0110
: 10 kHz
B
0111
: 20 kHz
B
1000
: 50 kHz
B
1001
: 100 kHz
B
1010
: 200 kHz
B
1011 to 1111
: Invalid
B
Technology module TM Count 2x24V (6ES7550-1AA01-0AB0)
Equipment Manual, 12/2020, A5E31870371-AC
Bit 2
Bit 1
Reaction to CPU STOP:
00
: Output substitute
B
value
1)
01
: Keep last value
B
10
: Continue operation
B
11
: Invalid
B
:
3
Bit 0

Advertisement

Table of Contents
loading

Table of Contents