Parameter data record
B.2 Parameter validation error
Error code in STATUS parame-
ter (hexadecimal)
Byte
Byte
Byte
Byte
0
1
2
3
DF
80
E1
1E
DF
80
E1
20
DF
80
E1
21
DF
80
E1
22
DF
80
E1
23
DF
80
E1
24
DF
80
E1
25
DF
80
E1
26
DF
80
E1
27
DF
80
E1
28
DF
80
E1
29
DF
80
E1
2A
DF
80
E1
2B
DF
80
E1
2C
DF
80
E1
2D
DF
80
E1
2E
DF
80
E1
36
DF
80
E1
37
98
Meaning
"Reaction to violation of a counting limit" pa-
rameter invalid
"Reaction to gate start" parameter invalid
1,5
Low counting limit > comparison value 0
Low counting limit > comparison value 1
1,5
Counting high limit < comparison value 0
Counting high limit < comparison value 1
"Start value" parameter invalid
"Low counting limit" parameter invalid
"Start value" parameter invalid
"High counting limit" parameter invalid
"Update time" parameter invalid
"Reference speed" parameter invalid
2
"Measured variable" parameter invalid
"Time base for velocity measurement" parame-
ter invalid
"Increments per unit" parameter invalid
"High counting limit" parameter invalid
"Low counting limit" parameter invalid
3
"Comparison value 0" parameter invalid
"Comparison value 1" parameter invalid
"Signal evaluation" parameter invalid
"Between comparison value 0 and 1" con-
figured for DQn.0
"Not between comparison value 0 and 1"
configured for DQn.0
"Between comparison value 0 and 1" con-
figured for DQn.1, but "Use by user pro-
gram" not configured for DQn.0
"Not between comparison value 0 and 1"
configured for DQn.1, but "Use by user pro-
gram" not configured for DQn.0
"Capture" configured for DIn.m in "Measuring"
operating mode
"Counting high limit" parameter invalid
4
4,5
"Comparison value 0" parameter invalid
"Comparison value 1" parameter invalid
Remedy
Enter valid parameter value.
Enter valid parameter value.
Low counting limit < comparison value 0
Low counting limit < comparison value 1
High counting limit > comparison value 0
High counting limit > comparison value 1
Enter valid parameter value:
Start value > low counting limit
Enter valid parameter value:
Start value < high counting limit
Enter parameter value from range 0 to 25000000
Enter parameter value from range 6.00 to
210000.00
.
D
Enter valid parameter value.
Enter valid parameter value.
Enter valid parameter value.
Enter valid parameter value:
Low counting limit < high counting limit
Enter valid parameter value:
Comparison value 0 < comparison value 1
Enter valid parameter value.
Configure "Between comparison value 0 and 1"
only for DQn.1
"Not between comparison value 0 and 1" config-
ured only for DQn.1
Only configure "Between comparison value 0 and
1" for DQn.1 when "Use by user program" is con-
figured for DQn.0
Only configure "Not between comparison value 0
and 1" for DQn.1 when "Use by user program" is
configured for DQn.0
Do not configure "Capture" for DIn.m in "Measuring"
operating mode.
Enter valid parameter value.
Enter valid parameter value.
Technology module TM Count 2x24V (6ES7550-1AA01-0AB0)
Equipment Manual, 12/2020, A5E31870371-AC
.