Rear Access Of The Panel - Siemens 8BT2 Installation And Operating Instructions Manual

Extendable truck- type circuit-breaker switchgear
Table of Contents

Advertisement

Fig65. Inserting the lower shutter tool
Precondition
Procedure
Fig68. Unscrewing lower bushing
4.3.9.1.2.
881-4027.9 * INSTALLATION AND OPERATING INSTRUCTIONS 8BT2 * Revision 04
Fig66. Lower shutter half way open
Completing cable installation from the front
DANGER!
Hazard due to human error
Protect your operating area.
Use warning signs and barrier tape to prevent unauthorized access.
Observe the Five Safety Rules.
• Lower shutter opening tool inserted and locked.
Remove 18x M10/M8 bolts from the lower bushing (fig68).
Remove the lower bushing (fig69).
Now. The cable compartment is reachable to do the connections
Rear access (Free standing version)
DANGER!
High Voltage!
Do not touch live components.
Ensure that the switchgear is only operated by qualified personnel who are familiar
with the operating instructions and observe the warnings.
Observe the five safety rules.
Fig67. Lower shutter fully open
Fig69. Access to the cable compartment
61