A
881-4027.9 * INSTALLATION AND OPERATING INSTRUCTIONS 8BT2 * Revision 04
truck to TEST position"
• High-voltage door open
• Padlocks available
• Lower shutter opening tool available (page21)
• Properly selected cable termination length (fig54 & 55). In the standard application, the
cable termination length should be max. 491mm. If longer one needs to be used, please
consult SIEMENS for the special design of deep bottom pan. The solution will be to adapt
the deep bottom pan as explained in clause 4.3.9.1.3. (page62). Dimensions of deep
bottom pan can be changed according to the cable termination length and diameter.
Fig54. Power cable location in the cable compartment
Cable lug
Cable
screen
Fig55. Power cable termination details
Dimensions of sealed power cable in [mm]
Maximum diameter (D)
Maximum cable termination length (A)
ATTENTION!
The cable compartment can be destroyed if cable termination with inadequate
dimensions is used.
Use only cable termination with the dimensions shown at above table.
Depending on the manufacturer of the cable terminations, the dimensions may
differ from those shown in fig54 & 55 and above table. If they are different, please
consult Siemens before installation.
D
A
80
491
Cable
compartment
57