Wiring; General Wiring Guidelines; Connection - Pilz PCOM sec br2 Operating Manual

Table of Contents

Advertisement

Wiring

7
Wiring
7.1

General wiring guidelines

Please note:
}
Information given in the
}
Use copper wire that can withstand 75° C.
}
The cable length of the cables connected to the inputs and output must be a max. of 30
m.
}
The supply of the module and the supply of the SC outputs are galvanically isolated.
}
Module supply:
– Polarity protection
– Overvoltage protection
Protect the supply voltage as follows:
– Circuit breaker, characteristic C - 6 A
– Blow-out fuse, slow, 6A
}
Supply to the SC outputs:
– Polarity protection
– No voltage stabilisation
7.2

Connection

Supply to the module X4
Input X3
Output X4
Operating Manual PCOM sec br2
1004534-EN-04
Technical details [
or
6 A
45]
must be followed.
Supply to the SC outputs X3
A1
A2
I0
24 V DC
O0
0 V
24 V DC
+ 24 V DC
0 V
| 20

Advertisement

Table of Contents
loading

This manual is also suitable for:

311502

Table of Contents