Commissioning; Wiring; General Wiring Guidelines; Connecting The Supply Voltage - Pilz SDD ES PROFIBUS Operating Manual

Table of Contents

Advertisement

SDD ES PROFIBUS

Commissioning

Wiring

General wiring guidelines

Please note:
}
Information given in the
}
Use copper wiring with a temperature stability of 75 °C.
}
External measures must be used to connect the
}
The device must be supplied from the same power supply as the connected safety
devices.
}
The power supply must meet the regulations for extra low voltages with protective elec-
trical separation (SELV, PELV).

Connecting the supply voltage

Connect the supply voltage to the fieldbus moduleSDD ES PROFIBUS :
}
24 V terminal: + 24 VDC
}
0 V terminal: 0 V

Connection to fieldbus

The connection to PROFIBUS-DP is made via a female 9-pin D-Sub connector in accord-
ance with the guidelines of the PROFIBUS User Group (PNO).
n.c. = not connected
Please note the following when connecting to PROFIBUS-DP:
}
Only use metal plugs or metallised plastic plugs
}
Twisted pair, screened cable must be used to connect the interfaces
Operating Manual SDD ES PROFIBUS
1003825-EN-06
Technical details [
20]
1: n.c.
2: n.c.
3: B (RxD/TxD-P)
5
9
4: CNTR-P
5: DGND
6: VP
6
7: n.c.
1
8: A (RxD/TxD-N)
9: n.c.
must be followed.
terminal to the functional earth.