Error Mode - Pilz PCOM sec br2 Operating Manual

Table of Contents

Advertisement

Operation
To reset or restore the system, proceed as follows:
1. Switch off the supply voltage to the device.
2. Connect the Ethernet interface X1 to the configuration PC.
Make sure that the connection is secure (e.g. direct network cable between Security-
Bridge and configuration PC), because the system is not HTTPS and password-protec-
ted in recovery mode.
3. Using a pointed object, press the red service button on the front of the device and keep
it held down.
4. Switch on the supply voltage while the service button is held down.
5. Let go of the service button when the Power LED lights up red.
6. Enter the default IP address http://192.168.222.1 in the browser.
The user interface opens in Recovery mode. This interface is only available in English.
7. To restore the system you can choose between the following options:
11.3

Error mode

If the system detects an internal error, it will switch to error mode.
Settings for how the system should behave in error mode can be made on the user inter-
face:
}
Availability
All data is forwarded
}
Security
No more data is forwarded
Operating Manual PCOM sec br2
1004534-EN-04
Firmware Recovery
The firmware is reset and restored. The configuration and event messages are re-
tained.
Upload the recovery firmware and then click on Firmware Update.
The system is restarted in operational mode.
Configuration Recovery
The system is reset to the factory settings. All the configuration data is deleted. All
the event messages are deleted.
Click on Configuration Recovery.
The system is then restarted in operational mode.
Reboot
Recovery mode is exited and the system is restarted in operational mode.