Huawei FusionModule1000A40 Product Description page 42

Prefabricated all-in-one data cente
Hide thumbs Also See for FusionModule1000A40:
Table of Contents

Advertisement

FusionModule1000A40 Prefabricated All-in-One
Data Center
Product Description (Advanced Configuration, 208
V)
Physical Ports
Table 3-13 Physical ports
Item
Refrigerant liquid pipe
Refrigerant gas pipe
Humidifier water inlet pipe
Installation Requirements
Table 3-14 Installation requirements
Item
Room door
Floor
Installation mode
Pipe and cable
routing
Equivalent length of
the one-way pipe
Height difference
between indoor and
outdoor units
Thermal insulation
foam thickness
Inner diameter of
thermal insulation
foam
Issue 03 (2021-02-10)
Specifications
Width ≥ 1.2 m; height ≥ 2.3 m
Bearing capacity ≥ 530 kg/m
≥ 250 mm
Installed on a concrete floor, a base, or an ESD floor
Top or bottom routing
≤ 100 m
● If the outdoor unit is placed higher than the indoor
unit, the vertical distance between them should be
less than or equal to 30 m.
● If the indoor unit is placed higher than the outdoor
unit, the vertical distance between them should be
less than or equal to 8 m.
≥ 13 mm
Liquid pipe: 16 mm
Gas pipe: 19 mm
Copyright © Huawei Technologies Co., Ltd.
Specifications
Copper pipe; outer diameter: 5/8 inch
(15.88 mm); wall thickness: 1.0 mm;
pressure withstanding capacity ≥ 4.5
MPa; welded
Copper pipe; outer diameter: 3/4 inch
(19.05 mm); wall thickness: 1.0 mm;
pressure withstanding capacity ≥ 4.5
MPa; welded
Reserved port: BSPP 1/2 inch; thread
connection
2
; height of the raised floor
3 Architecture
36