Data report configuration and sending period are as following:
Min Interval
(Unit:second)
Any number between
1~65535
FPort:0x07
Bytes
1
1
CmdID DeviceType
CmdID– 1 byte
DeviceType– 1 byte – Device Type of Device
NetvoxPayLoadData– var bytes (Max=9bytes)
Description
Device
Config
ReportReq
Config
ReportRsp
R313W
ReadConfig
ReportReq
ReadConfig
ReportRsp
(1)Configure R313W device parameters:
MinTime = 1min、MaxTime = 1min、BatteryChange = 0.1v
Downlink: 0106003C003C0100000000
Device returns:
8106000000000000000000(Configuration success)
8106010000000000000000(Configuration failed)
Max Interval
(Unit:second)
Any number between
1~65535
Cmd
Device
ID
Type
MinTime
0x01
(2bytes Unit:s)
0x81
0x06
0x02
MinTime
0x82
(2bytes Unit:s)
Reportable Change
Can not be 0.
Var (Fix =9 Bytes)
NetvoxPayLoadData
NetvoxPayLoadData
MaxTime
(2bytes Unit:s)
Status
(0x00_success)
(9Bytes,Fixed 0x00)
MaxTime
(2bytes Unit:s)
003C(H
= 60(D
ex)
ec)
5
Current Change≥
Reportable Change
Report
per Min Interval
BatteryChange
(1byte Unit:0.1v)
Reserved
(8Bytes,Fixed 0x00)
Reserved
BatteryChange
(1byte Unit:0.1v)
Current Change<
Reportable Change
Report
per Max Interval
Reserved
(4Bytes,Fixed
0x00)
Reserved
(4Bytes,Fixed
0x00)

Advertisement