MAGUIRE WEIGH SCALE BLENDER Installation Operation & Maintenance page 59

Hide thumbs Also See for WEIGH SCALE BLENDER:
Table of Contents

Advertisement

B L E N D E R 
W E I G H
S C A L E
M A G U I R E
P R O D U C T S ,
I N C .
Update Controller NET Software From USB Drive
Press (*,9,4) to initiate a NET specific software update from the USB Drive. Pressing *,9,4 will
cause the controller to search the USB drive for a folder named maguire and 2 files within the
folder maguire named: UPDATER.BIN and NETxxxxx.BIN. If more than one .BIN file exists in
the maguire folder, the controller will prompt you to select the version. Press the * key to toggle
between versions. Press the CE key to select the version you want to upload. The controller
will then verify the file. If verification is successful the controller will upload the new software.
DO NOT turn off the controller during this process. Wait until you see Update Complete! Then
turn off the controller and turn it back on again. The update should take only a few minutes.
Updated software is available from Maguire Products free of charge and can be obtained by
calling our office or visiting us on the web www.maguire.com.
SELECT COMM. SPEED (Set Baud Rate)
Press (*,9,5) to set the baud rate of the COM port. Options are 1200 baud or 2400 baud. Note:
The default baud rate is 1200. If the baud rate is set to 2400, the G2-SA (if in use will also have
to be set to 2400 baud by installing a jumper pin on an internal board. If you wish to do this,
contact Maguire Products and request the document regarding the G2-SA baud rate. Document
is also available online:
www.maguire.com
USBC Driver Version
Press (*,9,7) to display the USBC Driver version. Press * to update the driver from the Flash
drive. Press CE to verify the USB driver.
Display Load Cell Raw Signal (counts)
Press (*,9,8) to set flag for RAW-SIGNAL readout in place of gram readout of scale weight.
Power-On will always set this flag to OFF. Use the * key to toggle flag ENABLE or DISABLE.
Press EXIT when done. A raw signal readout is useful to demonstrate the extreme sensitivity of
the load cells. The raw signal readout bypasses the calibration math routine. Load cell function
can be monitored without concern for any improper weight calibration that may have been done.
Second line is an Output Event Monitor.
Enable Weight Calibration of the Load Cells
Press (*,9,9) to set flag to enable Weight Calibration of the Load Cells. In later model controllers
you can specify WSB CAL or LIW CAL. Power On will always set this flag to OFF. This flag must
be ON before the load cell weight calibration keys, ZERO and FULL WT, will function. With ON
flag displayed, press EXIT.
59

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents