Operational Limitations - York MILLENNIUM YCUL0045SC Installation Operation & Maintenance

Air-cooled condensing units hermetic scroll
Table of Contents

Advertisement

Installation
YCUL
0045SC
0061SC
0081SC
0095SC
0121SC
0125SC
0145SC
0161SC
0171SC
0185SC
0211SC
0235SC
0255SC
0275SC
NOTES:
1. For lower or higher suction temperature applications, contact your nearest YORK Office for application requirements.
2. For operation at temperatures below 25°F (-3.9°C), the optional Low Ambient Kit will need to be installed on the system.
3. For operation at temperatures above 115°F (46.1°C), the optional High Ambient Kit will need to be installed on the system.
VOLTAGE LIMITATIONS
The following voltage limitations are absolute and opera-
tion beyond these limitations may cause serious dam-
age to the compressor.
TABLE 8 – VOLTAGES
UNIT POWER
380-415/3/50
30

OPERATIONAL LIMITATIONS

ENGLISH UNITS
SUCTION
TEMPERATURE (°F)
MIN
1
MAX
1
35
55
35
55
35
55
35
55
35
55
35
55
35
55
35
55
35
55
35
55
35
55
35
55
35
55
35
55
MIN.
MAX.
342
440
AIR ON CONDENSER (°F)
MIN
2
MAX
3
0
125
0
125
0
125
0
125
0
125
0
125
0
125
0
125
0
125
0
125
0
125
0
125
0
125
0
125