Unit Limitations; Cooling Ratings - York YJ-30 Technical Manual

Split-system air-cooled condensing units, 30 thru 50 nominal tons
Hide thumbs Also See for YJ-30:
Table of Contents

Advertisement

628792-BTG-G-0418

Unit Limitations

Condenser Unit limitations
Nominal
Model
Tonnage
YJ-30
30
YJ-40
40
YJ-50
50
1
Rated in accordance with AHRI Standard 110, Range "A" Utilization Voltage.
2
Low Ambient accessories are available to permit stable system operation at ambient temperatures down to 0°F.

Cooling Ratings

Cooling Ratings
Condensing Unit Only
Outdoor
Unit
Gross Capacity
(MBH)
YJ-30
333
YJ-40
469
YJ-50
576
1
Condensing unit only ratings are at 45 F SST and
95 F entering-air temperature.
EER = Energy Efficiency Ratio at full load - the cooling capacity in Btu's per hour (Btuh) divided by the power input in watts, expressed in Btuh per
watt (Btuh/watt).
EER; condensing unit only ratings based on 45º F SST and 95ºF entering outdoor air temperature.
LEGEND
EER = Energy Efficiency Ratio
SST = Saturated Suction Temperature
Ducted Systems
Applied Voltage
Unit Voltage
2
Min
208/230-3-60
187
460-3-60
432
575-3-60
540
208/230-3-60
187
460-3-60
432
575-3-60
540
208/230-3-60
187
460-3-60
432
575-3-60
540
1
kW
EER
29.9
11.1
37.4
12.5
50.0
11.5
1
Outdoor DB Temp Cooling (°F) Indoor DB Temp Cooling (°F)
Max
Max
252
504
125
630
252
504
125
630
252
504
125
630
Min
Max
40
86
40
86
40
86
Min
68
68
68
7