York MILLENNIUM YCUL0045SC Installation Operation & Maintenance page 28

Air-cooled condensing units hermetic scroll
Table of Contents

Advertisement

Installation
(SINGLE POINT STANDARD ON YCUL0045 - 0121 MODELS; OPTIONAL ON YCUL0125 - 0275.
MODEL
VOLT
HZ
YCUL
0045SC 380/415
50
0061SC 380/415
50
0081SC 380/415
50
0095SC 380/415
50
0121SC 380/415
50
0125SC 380/415
50
0145SC 380/415
50
0161SC 380/415
50
0171SC 380/415
50
0185SC 380/415
50
0211SC 380/415
50
0235SC 380/415
50
0255SC 380/415
50
0275SC 380/415
50
See Notes on page 24.
28
ELECTRICAL DATA
SINGLE POINT POWER CONNECTIONS
DISCONNECT AND BREAKERS OPTIONAL ON ALL MODELS)
SINGLE POINT FIELD SUPPLIED WIRING
D.E. FUSE
MIN N/F
MCA
DISC SW
MIN
34
60
40
45
60
50
57
60
70
62
100
70
81
100
90
77
100
90
95
150
100
110
150
125
116
150
125
119
150
125
136
150
150
159
200
175
167
200
175
177
200
200
CKT. BKR.
MAX
MIN
MAX
SINGLE POINT
40
40
40
# 10 - # 6
60
50
60
# 8 - # 4
70
70
70
# 6 - # 2
80
70
80
# 6 - # 2
100
90
100
# 4 - # 1
90
90
90
# 4 - # 1
100
110
110
# 2 - 1/0
125
125
125
# 2 - 1/0
125
125
125
# 1 - 2/0
125
125
125
# 1 - 2/0
150
150
150
1/0 - 3/0
175
175
175
2/0 - 4/0
175
175
175
2/0 - 4/0
200
200
200
3/0 - 250
INCOMING WIRE RANGE
FACTORY SUPPLIED OPTIONAL
DISCONNECT
BREAKER
# 10 - # 6
# 10 - # 6
# 8 - # 4
# 8 - # 4
# 6 - # 2
# 6 - # 2
# 6 - # 2
# 6 - # 2
# 4 - # 1
# 4 - # 1
# 4 - # 1
# 4 - # 1
# 2 - 1/0
# 2 - 1/0
# 2 - 1/0
# 2 - 1/0
# 1 - 2/0
# 1 - 2/0
# 1 - 2/0
# 1 - 2/0
1/0 - 3/0
1/0 - 3/0
2/0 - 4/0
2/0 - 4/0
2/0 - 4/0
2/0 - 4/0
3/0 - 250
3/0 - 250
YORK INTERNATIONAL

Advertisement

Table of Contents
loading

Table of Contents