York MILLENNIUM YCUL0045SC Installation Operation & Maintenance page 107

Air-cooled condensing units hermetic scroll
Table of Contents

Advertisement

PRINT KEY
The PRINT key allows the operator to obtain a printout of
real-time system operating data or a printout of system
data at the "instant of the fault" on the last six faults
which occurred on the unit. An optional printer is required
for the printout.
OPERATING DATA PRINTOUT
Pressing the PRINT key and then OPER DATA key al-
lows the operator to obtain a printout of current system
operating parameters. When the OPER DATA key is
pressed, a snapshot will be taken of system operating
conditions and panel programming selections. This data
will be temporarily stored in memory and transmission
of this data will begin to the printer. A sample Operating
Data printout is shown below.
YORK INTERNATIONAL CORPORATION
MILLENNIUM CONDENSING UNIT
UNIT STATUS
2:04 PM
SYS 1
SYS 2
COMPRESSORS RUNNING
OPTIONS
AMBIENT CONTROL
LOCAL/REMOTE MODE
CONTROL MODE
LEAD/LAG CONTROL
FAN CONTROL
AMB & DSCH PRESS
PROGRAM VALUES
DSCH PRESS CUTOUT
SUCT PRESS CUTOUT
LOW AMBIENT CUTOUT
ANTI RECYCLE TIME
FAN CONTROL ON PRESS
FAN DIFF OFF PRESS
NUMBER OF COMPRESSORS
YORK INTERNATIONAL
01 OCT 97
NO COOLING LOAD
2
STANDARD
REMOTE
DISCHARGE AIR
AUTOMATIC
395 PSIG
44 PSIG
25.0 DEGF
600 SECS
230 PSIG
80 PSIG
6
UNIT DATA
DISCHARGE AIR TEMP
COOLING RANGE
55.0 +/- 5.0 DEGF
AMBIENT AIR TEMP
LEAD SYSTEM
EVAPORATOR PUMP
EVAPORATOR HEATER
ACTIVE REMOTE CONTROL
SOFTWARE VERSION
SYSTEM 1 DATA
COMPRESSORS STATUS
RUN TIME
0- 0- 0- 0 D-H-M-S
SUCTION PRESSURE
DISCHARGE PRESSURE
SUCTION TEMPERATURE
LIQUID LINE SOLENOID
HOT GAS BYPASS VALVE
CONDENSER FAN STAGES
SYSTEM 2 DATA
COMPRESSORS STATUS
RUN TIME
0- 0- 1-46 D-H-M-S
SUCTION PRESSURE
DISCHARGE PRESSURE
SUCTION TEMPERATURE
LIQUID LINE SOLENOID
CONDENSER FAN STAGES
DAILY SCHEDULE
S
M
T
W
T
F
S
SUN START=00:00AM
MON START=00:00AM
TUE START=00:00AM
WED START=00:00AM
THU START=00:00AM
FRI START=00:00AM
SAT START=00:00AM
HOL START=00:00AM
See Service And Troubleshooting section
for Printer Installation information.
FORM 150.63-NM2
58.2 DEGF
74.8 DEGF
SYS 2
ON
OFF
NONE
C.M06.01.01
OFF
66 PSIG
219 PSIG
52.8 DEGF
OFF
OFF
OFF
2
51 PSIG
157 PSIG
3
44.3 DEGF
ON
3
*=HOLIDAY
STOP=00:00AM
STOP=00:00AM
STOP=00:00AM
STOP=00:00AM
STOP=00:00AM
STOP=00:00AM
STOP=00:00AM
STOP=00:00AM
107