TABLE 31 – SUCTION TEMP. SENSOR
TEMPERATURE/VOLTAGE/
RESISTANCE CORRELATION
TEMP °F
VOLTAGE
0
1.71
2
1.78
4
1.85
6
1.93
8
2.00
10
2.07
12
2.15
14
2.22
16
2.30
18
2.37
20
2.45
22
2.52
24
2.59
26
2.67
28
2.74
30
2.81
32
2.88
34
2.95
36
3.02
38
3.08
40
3.15
42
3.21
44
3.27
46
3.33
48
3.39
50
3.45
52
3.51
54
3.56
56
3.61
58
3.67
60
3.72
62
3.76
64
3.81
66
3.86
68
3.90
70
3.94
72
3.98
74
4.02
76
4.06
78
4.10
80
4.13
YORK INTERNATIONAL
RESISTANCE
TEMP °C
25619
-18
24046
-17
22580
-16
21214
-14
19939
-13
18749
-12
17637
-11
16599
-10
15629
-9
14721
-8
13872
-7
13077
-6
12333
-4
11636
-3
10982
-2
10370
-1
9795
0
9256
1
8750
2
8276
3
7830
4
7411
6
7017
7
6647
8
6298
9
5970
10
5661
11
5370
12
5096
13
4837
14
4593
16
4363
17
4145
18
3941
19
3747
20
3564
21
3392
22
3228
23
3074
24
2928
26
2790
27