York MILLENNIUM YCUL0045SC Installation Operation & Maintenance page 26

Air-cooled condensing units hermetic scroll
Table of Contents

Advertisement

Installation
(SINGLE POINT ON YCUL0045 - 0121 MODELS; DUAL POINT ON YCUL0125 - 0275 MODELS)
SYSTEM #1 FIELD SUPPLIED WIRING
MODEL
VOLT HZ MCA MIN N/F
YCUL
DISC SW MIN
0045SC 380/415 50
34
60
0061SC 380/415 50
45
60
0081SC 380/415 50
57
60
0095SC 380/415 50
62
100
0121SC 380/415 50
81
100
0125SC 380/415 50
41
60
0145SC 380/415 50
58
60
0161SC 380/415 50
58
60
0171SC 380/415 50
65
100
0185SC 380/415 50
63
100
0211SC 380/415 50
83
100
0235SC 380/415 50
82
100
0255SC 380/415 50
92
100
0275SC 380/415 50
92
100
See Notes on page 24.
26
ELECTRICAL DATA
STANDARD POWER CONNECTIONS
INCOMING
D.E. FUSE
CKT. BKR.
WIRE
MAX
MIN MAX
RANGE
40
40
40
40
# 10 - # 6
50
60
50
60
# 8 - # 4
70
70
70
70
# 6 - # 2
70
80
70
80
# 6 - # 2
90
100
90
100
# 4 - # 1
45
50
45
50
# 8 - # 4
70
70
70
70
# 6 - # 2
70
70
70
70
# 6 - # 2
80
80
80
80
# 4 - # 1
70
80
70
80
# 6 - # 2
90
100
90
100
# 4 - # 1
90
100
90
100
# 4 - # 1
100
110
100
110
# 2 - 1/0
100
110
100
110
# 2 - 1/0
SYSTEM #1 COMPRESSOR & FAN
COMPR. #1
COMPR. #2
RLA
LRA
RLA
LRA
11.5
98
11.5
98
16.3
130
16.3
130
21.7
170
21.7
170
24.1
175
24.1
175
22.6
175
22.6
175
14.5
120
14.5
120
22.1
170
22.1
170
22.1
170
22.1
170
25.3
175
25.3
175
24.2
175
24.2
175
23.1
170
23.1
170
22.9
170
22.9
170
26.0
175
26.0
175
25.8
175
25.8
175
COMPR. #3
FANS
RLA LRA QTY FLA (EA)
2
3.8
2
3.8
2
3.8
2
3.8
22.6
175
2
3.8
2
3.8
2
3.8
2
3.8
2
3.8
2
3.8
23.1
170
2
3.8
22.9
170
2
3.8
26.0
175
2
3.8
25.8
175
2
3.8
YORK INTERNATIONAL