5.5.10. Connection for Ethernet communication

At the request of the installer, inverters may optionally incorporate hardware for communicating via ethernet. This
hardware is made up of an "AAX0004 Com Ethernet + RS-485" board.
The unit is provided with a >211 Ohm ferrite rod. The cable coming from the "AAX0004 Com
Ethernet + RS-485" board (RS-485 output) must be inserted as close as possible to the board,
turning it twice around the hole at its centre.
The board is provided with a bag (attached with a plastic tie) containing the Ethernet cable. Connect the cable to the
board's Ethernet output and feed it out through the holes on the upper left side of the enclosure.
See "AAX2002IKI01 Installation Guide for Communications Devices".
Follow the same instructions given in the previous point for the connection of the board to the control board.

5.5.11. Ground connections

The metal parts of the inverter (equipment ground) are electrically connected to the grounding bar on the front of the
cabinet.
To ensure the safety of personnel, this terminal must be connected to the installation's ground.