9.4.2. Temperature

Code
Alarm
0020H
Temperature
In the event of a shutdown with reason "Motivo Paro Temperatura", the first step is to check if the 0020H alarm
persists. If so, check the temperature of the unit's radiator via the display menu:
If the temperature displayed is close to or above 80 degrees, the unit has failed to inject power as a precau-
tion against a potentially damaging radiator temperature for the unit. The inverter will remain in this state until the
radiator has cooled, and then it will reconnect to the network.
If the problem occurs frequently, you should check the ventilation (fans and air intake grills) of the inverter and the
enclosure in which it is installed.
If the temperature shown is less than 140 °F (60 °C) and the alarm persists, the problem could be in the
ABB2000IKI01
J20
J27
Reason for shutdown
Power electronics temperature.
Auxiliary temperature sensor