CORNING Eclipse 01U Quick Start Manual

CORNING Eclipse 01U Quick Start Manual

Coupler shelf

Advertisement

Quick Links

01U

Table of Contents

1. General . ........................................................ 1
2. Description . .................................................. 1
3. Precautions . .................................................. 2
4. Components ................................................. 2
5. Shelf Installation .......................................... 3
6. Connector Access . ........................................ 3
7. Jumper Routing . ........................................... 3
8. Coupler Cassette Installation....................... 3
9. Identification Label . ..................................... 4
10. Connector Care............................................ 4
11. Specifications . ............................................... 5
1.

General

1.1
This instruction describes the installation
of the 01U and 02U Eclipse Coupler Shelf (ECS)
manufactured by Corning Cable Systems.
1.2
This document is being reissued to reflect new
hole configuration on the unit's mounting brackets.
p/n 009-222
Eclipse™ Coupler Shelf 01U - 02U
KPA-2556
2.

Description

2.1
The ECS is a fiber optic unit designed to house
couplers, splices, connectors, and fiber slack. The 01U
unit has 22 input/output ports and will fit in one rack
space on a standard utility rack. The 02U unit has 44
input/output ports and will fit in two rack spaces on a
standard utility rack (Figure 1).
2.2
Coupler shelf inputs and outputs can be pigtails
or adapters. When pigtails are specified, the standard
length is 3 meters (118 in.).
2.3
The unit is generally shipped completely
assembled to customer specifications. A label is
supplied that indicates the loss (in dBs) for each port.
2.4
The unit is designed to mount directly to a 19"
equipment rack. Use the 23" rack adapter brackets if
mounting to a 23" equipment rack.
Corning Cable Systems
SRP-009-222
Issue 3, April 2010
Page 1 of 5
02U
KPA-2549
Figure 1

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the Eclipse 01U and is the answer not in the manual?

Questions and answers

Summary of Contents for CORNING Eclipse 01U

  • Page 1 Corning Cable Systems SRP-009-222 Issue 3, April 2010 Page 1 of 5 Eclipse™ Coupler Shelf 01U - 02U KPA-2556 KPA-2549 Table of Contents 1. General ............1 Figure 1 2. Description ........... 1 Description 3. Precautions ........... 2 4. Components ..........
  • Page 2 Page 2 SRP-009-222 Issue 3 Precautions The wearing of safety glasses to protect the eyes from WARNING: Never look directly into the end accidental injury is strongly recommended when handling of a fiber that may be carrying laser light. Laser chemicals and cutting fiber.
  • Page 3 Figure 4 Coupler Cassette Installation Coupler Routing Guides Cassettes Knurled Nut KPA-2551 Attach for 23-in. Rack Application Figure 3 Figure 5 5.2 Determine the appropriate mounting position 8.1 Corning Cable Systems recommends that the for the unit and secure to frame using the proper ECS be ordered fully configured before installing into a hardware. Ensure the unit is pushed back as far as the rack. This keeps jumpers and internal fibers from being sliding brackets will allow. disturbed. 8.2 If the coupler circuit must change, coupler Connector Access cassettes can be removed from and added to the unit by the following (refer to Figure 5): In some applications, the ECS must be extended forward to provide access to the input/output adapters. • Disconnect jumpers and remove them from external This is accomplished by gripping the jumper trough on routing guides to avoid damage when the unit is each side and firmly pulling the unit forward.
  • Page 4 Page 4 SRP-009-222 Issue 3 Identification Label KPA-2553 Figure 6 10. Connector Care A label is provided to identify transmitter inputs (Tx), node outputs, power levels (insertion loss), and Connectors are extremely delicate devices. Therefore miscellaneous descriptions associated with each I/O the following precautions should always be observed. port (Figure 6). • At installation, use a clean tissue soaked in isopropyl 9.2 To access the label card, pull up at the tab in the alcohol to gently clean the connectors at the end center of the shelf. The card may be pulled completely of the jumper or pigtail. Clean all the areas of the out of the unit to write information on the label connector that will contact the connector sleeve. (Figure 6). • Do not press on connectors as you clean. Doing so 9.3 The “Loss (dB)” information is always included may scratch or crack the connector surface, making and represents the measured insertion loss of each it unusable. port. All other information can be added as required. • Carefully press the connector into its receptacle and tighten. Do not overtighten. Doing so can damage the connector surface. • Do not allow the connector body (ferrule) to turn as you screw it into place. Doing so will allow the surfaces to grind against each other causing...
  • Page 5 SRP-009-222 11. Specifications 17.09 inches 1.63 inches 8.08 inches 20.3 inches 3.92 inches 17.09 inches 4.40 inches KPA-2549 8.06 inches 3.92 inches 20.3 inches Figure 8 Corning Cable Systems reserves the right to improve, enhance, and modify the features and specifications of Corning Cable Systems’ products without prior notification. All trademarks are property of their respective holders. Corning Cable Systems is certified ISO 9001. ©1997, 2000, 2010 Corning Cable Systems LLC. All rights reserved. Special Note: Fiber Optic Training Program Corning Cable Systems LLC Corning Cable Systems offers comprehensive, integrated training programs. PO Box 489 Courses are structured for: telephony, CATV, LAN, Intelligent Transportation Hickory, NC 28603-0489 USA Systems and Power Utilities. FAX: 828-327-5973 For information on Engineering Services Training call: 800-743-2671.

This manual is also suitable for: