Installation Guide
Power Monitoring
E30E Series
Installation (cont.)
Z206792-0B
Page 8 of 24
Alta Labs, Enercept, Enspector, Hawkeye, Trustat, Aerospond, Veris, and the Veris 'V' logo are trademarks or registered trademarks of Veris Industries, L.L.C. in the USA and/or other countries.
Shop for Power Metering products online at:
3. Verify that the serial numbers printed on the current sensor strips and on the E30E match. The board and the strips are sold as a
calibrated set.
4. Install the E30E in the panel (hardware not provided). A grounding connection is located on the housing (see below). Use this
stud to ground the device when it is mounted on a nonconductive surface.
Panel 2
Panel 1
5. Connect the current sensor ribbon cables to the 50-pin connectors on the E30E. The label on the strip indicates which connector
to use on the E30E (e.g. connect the strip labeled "Panel 1A" to the bottom right connector on the board). Orient the cables so
that the plastic key on the E30E connector aligns with the keyhole cutout on the ribbon cable connector, as shown below.
Panel 2,
Strip B
Panel 2,
Strip A