2. BACnet IP mode
BACnet IP mode uses the same DeviceID_Offset and Virt_Router_Net parameters described above for BACnet MS/TP mode. One
additional parameter, BACnet_IP_Port, is used to set the UDP port. Most BACnet systems use the default port (47808 decimal,
0xBAC0 hex) that is recommended in the BACnet standard as the only UDP port. Some large systems need to segment the
enterprise and use more than port. If so, enter the number of the port you need to use to access this device. BACnet IP mode does
not use MSTP_Max_Master or MSTP_MAC_Addr.
BACnet IP mode adds another field called BBMD_Enable. See the section BBMD Support for a full description of how to enable and