Data Outputs (cont.)
Solid-Core Current
Sensors
Z206792-0B
Page 6 of 24
Alta Labs, Enercept, Enspector, Hawkeye, Trustat, Aerospond, Veris, and the Veris 'V' logo are trademarks or registered trademarks of Veris Industries, L.L.C. in the USA and/or other countries.
Shop for Power Metering products online at:
• Demand/snapshot time interval source: The E30E offers two mechanisms for driving the demand/snapshot time
interval, an interval timer or an RTC (real-time clock). The legacy mode (default) uses an interval timer that does not
need to be set to an absolute time. When using the interval timer the demand/snapshot interval can be set from
10 to 32767 seconds (over 9 hours). An alternate mode utilizes an RTC set to a specific date and time to synchronize
the results with a larger system. The RTC must first be set in order to run and capture demand values and energy
snapshots. When power is interrupted, the RTC resets to a default date and time and must be set again in order to run.
When using the RTC, the demand/snapshot interval can be set from 10 to 3600 seconds (1 hour).
Current: multi-phase average and per phase
Current phase angle
Real power (kW): multi-phase total and per phase
Apparent power (kVA): multi-phase total and per phase
Real Time Measurements
Power factor: multi-phase average and per phase
Voltage - L-L: multi-phase average and per phase
Voltage - L-N: multi-phase average and per phase
Frequency (phase A)
Current present demand: multi-phase average and per phase
Demand Measurements
Real Power (kW) present demand: multi-phase average and per phase
Maximum instantaneous current: multi-phase average and per phase
Historic Maximums
Maximum current demand: multi-phase average and per phase
Maximum real power demand: multi-phase total and per phase
Accumulated Energy
Energy (kWh): multi-phase total and per phase
Energy Snapshots
Energy (kWh): multi-phase total and per phase
Current: multi-phase average and per phase
Current phase angle per branch
Real Time Measurements
Real power (kW): multi-phase total and per phase
Apparent power (kVA): multi-phase total and per phase
Power factor: multi-phase average and per phase
Current present demand: multi-phase average and per phase
Demand Measurements
Real power (kW) present demand: multi-phase average and per phase
Maximum instantaneous current: multi-phase average and per phase
Historic Maximums
Maximum current demand: multi-phase average and per phase
Maximum real power demand: multi-phase total and per phase
Accumulated Energy
Energy (kWh): multi-phase total and per phase
Energy Snapshots
Energy (kWh): multi-phase total and per phase
Voltage over/under
Branch current over/under
Alarms
Mains current over/under
100 A Solid-Core Current Sensor
Voltage Rating
300 VAC
Temperature
0° to 60°C
Agency
EN61010-1
©2014 Veris Industries USA 800.354.8556 or +1.503.598.4564 / support@veris.com
PowerMeterStore
Other companies' trademarks are hereby acknowledged to belong to their respective owners.
www.
Monitoring of Mains
Monitoring of Branch Circuits
Modbus Alarms
04142
1.877.766.5412
.ca
TM

Advertisement

loading