Positioning The Probe - Electrode; Combustion Head Adjustment; Air Adjustment - Riello RS 55/E BLU Installation, Use And Maintenance Instructions

Forced draught gas burners
Table of Contents

Advertisement

Available languages

Available languages

5.7

Positioning the probe - electrode

If in the previous check the position of the probe or electrode was
not correct, remove the screw 1)(Fig. 14) extract the inner part
2)(Fig. 14) of the head, and adjust them.
Do not rotate the probe, leave it as in (Fig. 15);
since if it is located too close to the ignition elec-
trode, the control box amplifier may be damaged.
CAUTION
5.8

Combustion head adjustment

At this stage of installation the blast tube and the pipe coupling
are secured to the boiler as shown in A)(Fig. 16).
Therefore the adjustment of the combustion head is particularly
easy, an adjustment that depends solely on the maximum power
of the burner.
Therefore, this value must be set before adjusting the combus-
tion head.
Two adjustments of the head are foreseen:
the air R1 ( A , Fig. 16)
the gas/air R2 ( B , Fig. 16)
In the diagram of (Fig. 17), find the notch at which both the air
and gas should be adjusted.
5.8.1

Air adjustment

Rotate the screw 4)(Fig. 16) until the notch you have found cor-
responds with the front surface 5)(Fig. 16) of the flange.
To facilitate the adjustment, loosen the screw 6)
(Fig. 16), adjust, then block.
CAUTION
20040563
Installation
1
3
2
PROBE
D1209
A
20
GB
D8150
ELECTRODE
D1256
Fig. 14
Fig. 15
B
Fig. 16

Advertisement

Chapters

Table of Contents
loading

This manual is also suitable for:

20038488200384912003848920038492