Gas Feeding Line - Riello RS 55/E BLU Installation, Use And Maintenance Instructions

Forced draught gas burners
Table of Contents

Advertisement

Available languages

Available languages

5.9.2

Gas feeding line

D3791
Key (Fig. 20)
1
Gas input pipe
2
Manual valve
3
Vibration damping joint
4
Pressure gauge with pushbutton cock
5
Multibloc, including:
- filter (replaceable)
- working valve
- pressure adjuster
6
minimum gas pressure switch
7
Valve leak detection control device. In compliance with the
EN 676 standard, gas valve leak detection control devices
are compulsory for burners with maximum outputs over 1200
kW.
8
Gasket
9
Gas adjustment butterfly valve
10 Maximum gas pressure switch (accessory)
11 Gas train/burner adaptor
P1 Pressure at combustion head
P2 Upstream pressure of valves/adjuster
P3 Upstream pressure of the filter
L
Gas train supplied separately with the code indicated in Tab. J.
L1 The responsibility of the installer
Installation
6
4
P2
1
2
3
L1
9
7
P1
5
11
L
Make sure that the gas train is properly installed
by checking for any fuel leaks along the fuel sup-
ply line.
WARNING
23
GB
10
8
Fig. 20
20040563

Advertisement

Chapters

Table of Contents
loading

This manual is also suitable for:

20038488200384912003848920038492

Table of Contents