Baxi LUNA3 SYSTEM HT 1.180 MP Installers And Users Instructions page 59

Wall-mounted condensing boilers
Table of Contents

Advertisement

Available languages
  • EN

Available languages

  • ENGLISH, page 36
To simplify calibration of the gas valve, the "calibration function" can be set directly on the boiler control panel by pro-
ceeding as follows:
1) Press the
keys (2-3) together until the display shows the pointer " " alongside the
ds).
2) Press the
keys to set the fan speed at the minimum and maximum heat output (%PWM);
N.b - to set the minimum and maximum heat output quickly, press the
3) press either of the two
Figure 15
IMportant:
in the case of conversion from natural gas to propane (LPG), the following operations must be performed
before calibrating the gas valve as illustrated above:
• Turn adjuster screw (V) on the gas valve through the number of complete revolutions specified in table 3 or 3.1;
• On the control panel display set ignition power parameters H608 and H611. The values to be input are given in table 3
or 3.1. The programming methods are described in chapter 17;
Luna3 sYsteM ht 1.330 Mp
CO
max. heat output
2
CO
min. heat output
2
CO max
Gas nozzle
table 1a
Luna3 sYsteM ht 1.240 Mp
CO
max. heat output
2
CO
min. heat output
2
CO max
Gas nozzle
table 1b
Luna3 sYsteM ht 1.180 Mp
CO
max. heat output
2
CO
min. heat output
2
CO max
Gas nozzle
table 1c
InstructIons pertaInInG to the InstaLLer
keys to exit the function..
G20 - 2h - 20 mbar
8,7%
8,4%
< 250 ppm
12,0 mm
G20 - 2h - 20 mbar
8,7%
8,4%
< 250 ppm
7,5 mm
G20 - 2h - 20 mbar
8,7%
8,4%
< 250 ppm
5,7 mm
keys respectively;
G31 - 3p - 37 mbar
10%
9,8%
< 250 ppm
12,0 mm
G31 - 3p - 37 mbar
10%
9,5%
< 250 ppm
7,5 mm
G31 - 3p - 37 mbar
10%
9,5%
< 250 ppm
5,7 mm
59
symbol (about 6 secon-
925.916.2 - GB