10.5 Settings for pressure monitoring
10.5.1 Limit monitoring OUT1 or OUT2 / hysteresis function
► Select [SELx] and set PRES�
► Select [oux] and adjust the switching signal:
- Hno = hysteresis function / normally open
- Hnc = hysteresis function / normally closed
► Select [SPx] and set the value at which the output is set�
► Select [rPx] and set the value at which the output is reset�
10.5.2 Limit monitoring OUT1 or OUT2 / window function
► Select [SELx] and set PRES�
► Select [oux] and adjust the switching signal:
- Fno = window function / normally open
- Fnc = window function / normally closed
► Select [FHx] and set the upper limit of the window section�
► Select [FLx] and set the lower limit of the window sector�
10.5.3 Analogue signal pressure OUT2
► Select [SEL2] and set PRES�
► Select [ou2] and select analogue signal: I (4...20 mA)
► Select [ASP2] and set the value at which 4 mA is provided�
► Select [AEP2] and set the value at which 20 mA is provided�
40
Menu OUTx:
[SELx]
[oux]
[SPx]
[rPx]
Menu OUTx:
[SELx]
[oux]
[FHx]
[FLx]
Menu OUT2:
[SEL2]
[ou2]
[ASP2]
[AEP2]