• Altitude: 0000 – 2000, US 2001 – 3000, CN 2100 – 4500, US 3001 – 4000, US 4001 – 5000,
US 5001 6000, US 6001 – 7000, US 7001 – 8000, US 8001 – 9000, and US > 9000. Default
= US 2001-3000
• Static Pressure selection: 0 to 10,000 ft. This value is used to correct the static pressure
readings the system performs.
6.3.3.7. Furnace Dehumidifier Drain
This option selects the time the continuous fan turns off at the end of cooling in order to drain
the indoor coil of water (Smart Evapt feature). The fan will only be turned off if a dehumidify
demand existed at the start of or during the cooling cycle.
• Dehumidify Drain Time: Adjustable from 5 to 60 minutes. Default = 15 minutes
6.3.3.8. Furnace G Terminal
This setup option selects desired operation when the R-G circuit changes state on the furnace
control board depending on setup.
Under the function option, FAN turns on fan to selected fan speed when G terminal is
energized. SHUTDOWN shuts off fan and equipment when initiated.
After the selections are made, touch SAVE.
• Function: Disabled, Fan or Shutdown. Default = Disabled
• Fan Speed: Low, Med, or High. Default = Low
• Shutdown:
– Normally Open
– Normally Closed
– The shutdown function may not be immediate. Blower off delays, etc., will still be used.
The shutdown is not intended for commercial applications. If immediate shutdown is
required, provision must be made to remove power to indoor unit.
6.3.3.9. Furnace G-Terminal Alert
Use the alert function to select the contact state for an alert. Select Normally Open or
Normally Closed, and then save your selection.
30
A13230
Need help?
Do you have a question about the Evolution Connex Control and is the answer not in the manual?
Questions and answers