6.3.1.3. Offsets
This option allows calibration (or deliberate miscalibration) of the temperature and humidity
sensors. These offsets are added to the actual temperature/humidity values. See also Zone
Offsets Section. When the correct offsets are made, touch SAVE. If the system is non-zoned, the
indoor temperature offset is found on this screen. If the system is zoned, the indoor temperature
offset is found in the Zoning, Offsets screen.
• Outdoor temperature: Adjustable from -5 to 5°F (-3 to 3°C). Default = 0°F
• Indoor temperature: Adjustable from -5 to 5°F (-3 to 3°C). Default = 0°F
• Humidity: Adjustable from -10 – 10%. Default = 0%
NOTE: For single-zone systems, the indoor temperature offset is on this screen. For zoning
systems, there is a separate zone indoor temperature offset screen in the zoning menu.
Single-zone Systems
6.3.1.4. Reset Factory Defaults
This option allows the installer to reset certain factory parameters. After the selections are
made, touch SAVE.
• Program Schedule: Reset back to pre-programmed time and temperature.
• User Settings: Reset user settings back to pre-programmed values.
• Install Settings: Reset installation settings back to pre-programmed values.
• Last 10 Events: Reset the last 10 system events under the Service menu.
Zoning Systems
24
Zoning Systems
A190275