Point List; Sequence Of Operation - Automated Logic RC642 Technical Instructions

Room controller
Table of Contents

Advertisement

Point list

Point Name
Zone temp
Zone setpoint
adjust
Zone override
Smoke detector
Discharge temp
Freezestat
Fan status
Cooling stage 1
Heating stage 1
Heating stage 2
Fan speed 1
Fan speed 2
Fan speed 3
Chilled water valve
Hot water valve
Sequence of
Run conditions - scheduled
operation
User-defined schedules determine when the unit runs in:
Hardware Points
AI
X
X
X
Occupied Mode
The unit maintains a 74°F (23.5°C) adjustable cooling setpoint and a 70°F (21°C)
adjustable heating setpoint.
Unoccupied Mode (night setback)
The unit maintains an 85°F (29.5°C) adjustable cooling setpoint and a 55°F (13°C)
adjustable heating setpoint.
BI
BO AO I/O #
Internal
Internal
X
Internal
X
UI-1
UI-2
X
UI-3
X
UI-4
X
DO-1 (Y1)
X
DO-4 (W1)
X
DO-5 (W2)
X
DO-3 (G)
X
DO-6
X
DO-2 (Y2)
X
AO-1
X
AO-2
71
Comments
Optional – Requires sensor (dry
contact)
Optional – Requires sensor
(Type II thermistor)
Optional – Requires sensor (dry
contact)
Optional - Dry contact
NOTE Short input to ground if
not used.
Optional – Use this output OR
chilled water valve
Optional – Use this output OR
hot water valve
Optional – Use this output if
2-stage heating is present
Relay output
Relay output
Relay output
Optional – 0–10 Vdc
Use this output OR
staged
cooling
Optional – 0–10 Vdc
Use this output OR staged
heating