Table of Contents
loading
Need help?

Need help?

Do you have a question about the M4106nx and is the answer not in the manual?

Questions and answers

Subscribe to Our Youtube Channel

Summary of Contents for Automated Logic M4106nx

  • Page 1: Table Of Contents

    Protection 10 Production Date 10 Automated Logic Corporation • 1150 Roberts Blvd. • Kennesaw, GA 30144 • 770/429-3000 • 770/429-3001 Fax • www.automatedlogic.com • Copyright 2000 Automated Logic Corporation. All rights reserved. Automated Logic, the Automated Logic logo, SuperVision, Eikon, and Alert are registered trademarks of Automated Logic Corporation.
  • Page 2: Using The M4106Nx

    I/O connections. equipment in a residential area is likely to cause harmful interference in which case the The M4106nx uses a 6.00g or later version of user will be required to correct the the MNM Module Driver; for more interference at his own expense.
  • Page 3: Specifications

    Power 24VAC ± 10%, 50-60Hz (24VAC Before setting or changing the address, make ±10%, 60Hz for UUKL Smoke Control sure the M4106nx’s power is off. The Systems), 20VA power consumption M4106nx only reads the address when the single Class 2 source only, 100VA or less.
  • Page 4: Cmnet Communications

    On an ARC156 CMnet (156 kbps), set the CMnet Communications CMnet Mode jumper to ARC156 (see The M4106nx module can connect to the Figure 4 for the switch’s location). CMnet at 9600 bps, 38.4 kbps, or 156 kbps. When communicating at 156 kbps, the CMnet...
  • Page 5: Communicating With The Workstation

    You can verify that the M4106nx is The Access Port’s baud rate is determined by communicating on the CMnet by making sure the baud rate DIP switch on the module. the CMnet transmit and receive LEDs are 1. Connect the computer’s serial port to the active (see Figure 5 for location).
  • Page 6 The M4106nx accumulates up to ten input pulses per second. Figure 7. Input Wiring channel numbers are listed in “Channel 1. Be sure the M4106nx’s power is off before Numbers” on page 8. wiring any inputs or outputs. 5. To verify each input’s operation, have 2.
  • Page 7: Digital Outputs

    FB closed, according to the jumper setting. output open closed programming Be sure the M4106nx’s power is off before Status page result (use wiring any inputs or outputs. Connect the channel output wiring to the screw terminals on the...
  • Page 8: Channel Numbers

    0.00 15.88 Thermistor Figure 10. Analog Output Wiring -27° to 100.6° C 0.00 15.69 Be sure the M4106nx’s power is off before UI 5 0 to 20mA mA or Volts § § 0 to 5V wiring any inputs or outputs. Connect the...
  • Page 9: Transferring Memory

    Transferring Memory The M4106nx module can store up to 59 1. Turn the module’s power off. Make sure Function Blocks (FBs) and the MNM module the module’s address switches are not set driver.
  • Page 10: Protection

    Power - lights when power is being supplied Protection to the module. The M4106nx module is protected by internal solid state Polyswitches on the incoming Rx - lights when the module receives data power and CMnet. These Polyswitches are from the CMnet.