10. Upper Current Limitation Mode

Serial-parallel I/O must be connected in order to perform upper current limitation mode. The below input is
received by serial-parallel I/O, and upper current limitation mode is performed.
The upper current limitation values can be set as needed with serial-prallel I/O.
Upper current
limitation setting
Contact 1 Contact 2
No control
Operates to XX% of the upper limit for the rated
current.
Operates to XX% of the upper limit for the rated
current..
Always in stop condition.
: Input present
* The rated current indicates the current value that is listed in the catalog or similar material.
* XX is able to set in EEPROM of main outdoor unit.
EEPROM setting in main outdoor unit
CODE: 1A, 1B
Demand setting
Contact 1 Contact 2
No limit
Demandcanbesetfrom40–200%at EEPROM1A.
Demandcanbesetfrom40–200%at EEPROM1B.
Remainsstopped.
* A1 has to be bigger than A2.
Control
: Input not present
Control
Control Functions-Outdoor Unit
Operates to the
maximum capacity.
Current is limited to the set values.
Current is limited to the set values.
1 - 31
2WAY SYSTEM
Upper current limitation meaning
Operates to maximum capacity.
-
-
-
Demand meaning
-
1