Panasonic U-8ME1E8E Service Manual page 158

2way system
Table of Contents

Advertisement

4. 2WAY Alarm Codes
F16 Alarm
Alarm code
F16
Alarm meaning
High-pressure sensor trouble (abnormal rise in high pressure) (In some cases this may not be
the result of a high-pressure sensor malfunction.)
Alarm conditions
High-pressure SW activated although the detected pressure was lower (3.03 MPa or below)
than the high-pressure SW activation pressure: Undershift
High-pressure SW failed to activate although the detected pressure was higher (3.43 MPa or
above) than the high-pressure SW activation pressure: Overshift
The saturation temperature at the detected pressure is 5°C or more below the highest indoor-
unit E1 temperature continuously for 30 minutes.
High-pressure sensor disconnected or open circuit.
Probable cause
(1) High-pressure sensor malfunction
(2) Failure to connect the connector to the outdoor unit PCB
(3) Failure to open the service valve
(4) Clogged tubing
(5) Valve leakage
(6) Over-charging
(7) Outdoor unit PCB failure
(8) Electrical noise
Check
(1) High-pressure sensor failure
Check the sensor resistance value. (Use a tester and measure the resistance between
sensor No. 1 and No. 3)
Resistance of less than 10kΩ indicates a short circuit or other trouble.
Resistance of 10kΩ - 200kΩ is normal. Resistance of more than 200kΩ indicates
an open circuit or other trouble.
Connect a gauge to the high-pressure outlet and check for changes in the value
dispalyed by the monitoring software, and for large deviation of the gauge pressure.
During heating, check whether the temperature is lower than the highest indoor-unit E1
temperature.
* The pressure detected by the high-pressure sensor is the highest pressure in the system.
(2) Failure to open the service valve, clogged tubing, valve leakage, over-charging.
In all of these cases an alarm occurs when there are rapid pressure fl uctuations and tracking
of the detected pressure is poor.
Check the open/closed status of the valve.
Check for clogging of the tubing.
To check for clogging, disconnect the high-pressure sensor from the PCB and check
whether the high-pressure SW activates.
Check for valve leakage and over-charging
When valve leakage or over-charging occurs, refrigerant is likely to accumulate in the
oudoor units or indoor units, resulting in a sudden rise in pressure at start that occurs
before the refrigerant in the heat exchanger is discharged.
* The representative valves to check are the liquid valves and mechanical valves.
(3) Outdoor unit PCB failure
The check items are the same as for a high-pressure sensor malfunction.
A normal PCB is needed to determine whether the problem is a PCB failure or a pressure
sensor malfunction. If an abnormality was found at the check items for a high-pressure
sensor malfunction, fi rst try replacing the PCB and check again.
Therefore during heating the converted saturation temperature will never be lower than
any indoor-unit E1 temperature. During cooling this temperature will never be lower
than the outdoor unit liquid temperature.
Trouble is corrected: Outdoor unit PCB failure
Trouble is not corrected: High-pressure sensor malfunction
6 - 15
2WAY SYSTEM
Trouble Diagnosis
6
Continued

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents