4. 2WAY Alarm Codes
With type 8HP, the INV compressor is compressor 1 only.
With types 10HP, 12HP, 14HP and 16HP, the INV compressor is compressor 1, and the
constant-speed compressors (AC1) are compressors 2 .
With types 18HP and 20HP, the INV compressor is compressor 1, and the constant-speed
compressors (AC1, AC2) are compressors 2 and 3.
Alarm code
E06
Outdoor unit failed to receive serial communication signals from indoor unit.
E12
Automatic address setting start is prohibited.
E15
Automatic address setting alarm (too few units)
E16
Automatic address setting alarm (too many units)
E20
No indoor units at automatic address setting.
E24
Outdoor unit (INV) failed to receive communications from another outdoor
unit (constant-speed).
E25
Outdoor unit address setting failure (duplication)
E26
Mismatch in outdoor unit quantity
E29
Outdoor unit failed to receive communication from outdoor unit (main)
E31
Communication error between the microcomputers
F04
Compressor 1 discharge temperature sensor trouble
F05
Compressor 2 discharge temperature sensor trouble
F22
Compressor 3 discharge temperature sensor trouble
F06
Gas temperature sensor trouble at outdoor heat exchanger 1 (In)
F07
Liquid temperature sensor trouble at outdoor heat exchanger 1 (Out)
F08
Outdoor air temperature sensor trouble
F12
Compressor intake temperature sensor trouble
F16
High-pressure sensor trouble
F17
Low-pressure sensor trouble
F23
Gas temperature sensor trouble at outdoor heat exchanger 2 (In)
F24
Liquid temperature sensor trouble at outdoor heat exchanger 2 (Out)
F31
Outdoor unit non-volatile memory (EEPROM) trouble
H11
Constant speed compressor 2 overcurrent alarm
H12
Constant speed compressor 2 lock current alarm
H03
Compressor 1 CT sensor disconnected or short-circuit
H05
Compressor 1 discharge temperature sensor disconnected
H06
Low-pressure switch activated
H08
Compressor 1 oil detection sensor (connection) trouble
H13
Compressor 2 CT sensor disconnected or short-circuit
H15
Compressor 2 discharge temperature sensor disconnected
H21
Compressor 3 overcurrent alarm
H22
Compressor 3 lock current alarm
H23
Compressor 3 CT sensor disconnected or short-circuit
H25
Compressor 3 discharge temperature sensor disconnected
H27
Compressor 2 oil detection sensor (connection) trouble
H28
Compressor 3 oil detection sensor (connection) trouble
H31
HIC trouble alarm
L04
Outdoor system address duplication
L10
Outdoor unit capacity not set
L17
Outdoor unit model mismatch
L18
4-way valve operation failure
Alarm meaning
6 - 7
2WAY SYSTEM
Trouble Diagnosis
P
a
g
e
6 -9
6 -9
6 -9
6 -10
6 -10
6 -10
6 -11
6 -11
6 -11
6 -11
6 -12
6 -12
6 -12
6 -13
6 -13
6 -14
6 -14
6 -15
6 -16
6 -13
6 -13
6 -16
6 -17
6 -17
6 -18
6 -18
6 -19
6 -20
6 -18
6 -18
6 -17
6
6 -17
6 -18
6 -18
6 -20
6 -20
6 -21
6 -21
6 -22
6 -22
6 -22