Panasonic U-8ME1E8E Service Manual page 163

2way system
Table of Contents

Advertisement

4. 2WAY Alarm Codes
H08, H27, H28 Alarm
Alarm code
Alarm meaning
Alarm conditions
Probable cause
Check
Correction
Example
Notes
6
H08, H27, H28
Trouble (open circuit) with the oil sensor (connection) at compressor 1, compressor 2,
or compressor 3
This alarm occurs when a connector connection (pins 1 and 2 for compressor 1, pins 4
and 5 for compressor 2, and pins 7 and 8 for compressor 3) is open.
Disconnected connector
Check that the connector is securely connected.
(1) Connect the connector.
(2) Correct the connection at connector pins 4 and 5.
6 - 20
2WAY SYSTEM
Trouble Diagnosis