Panasonic U-8ME1E8E Service Manual page 51

2way system
Table of Contents

Advertisement

80 –FF: Outdoor unit parameters
DN
80 Invalid
81 Outdoor unit capacity
1
82
|
Invalid
86
87 Max. inverter Hz of compressor
88 Min. inverter Hz of compressor
89 Invalid
8E Invalid
8F High Static Pressure Mode
90
|
Invalid
96
9A Invalid
9B Invalid
A0 Invalid
A1 Invalid
A2 Invalid
A3 The minimum operating time until defrosting
A4 Factory use
A5 Continuance time of fan step "0"
A6 Factory use
A7 Capacity fi ne-tuning with MOV of indoor unit
A8 Invalid
Indoor min. MOV pulse shift under SH control
A9
(for indoor unit capacity 5.6kW or less)
Indoor min. MOV pulse shift under SH control
AA
(for indoor unit capacity 7.3kW)
Indoor min. MOV pulse shift under SH control
AB
(for indoor unit capacity over 10.6kW)
AD Max time of defrosting control
B1 Pre-trip counts until "H06" alarm
B2 Invalid
B3 Pre-trip counts until "P03" alarm
B4 Pre-trip counts until "P17" alarm
B5 Pre-trip counts until "P18" alarm
B8 Factory use
B9 Factory use
BA Outdoor min. MOV1 pulse shift under SH control
BB Outdoor min. MOV2 pulse shift under SH control
BC Invalid
BD Invalid
BE Invalid
Item
1 - 44
Control Functions - Outdoor Unit
Setting No
-
0, 22, 25, 28, 32, 36, 40, 45, 50, 56, 63, 71, 80, 90,
100, 112, 125, 140, 160, 180, 200, 224(8HP), 250,
280(10HP), 335(12HP), 355, 400(14HP), 450(16HP),
500(18HP), 560(20HP), 600, 630, 670, 710, 800, 840
-
0, 5, 10, 15,,, ,,, 115, 120(P)
0, 5, 10, 15(P),,, ,,, 115, 120
-
-
0(P)=Valid, 1=invalid, 2-6=No use
(For detail refer to 5-7)
-
-
-
-
-
-
20, 21, 22, 35(P),,, ,,, 89, 90
(For detail refer to 9-4)
-
2, 3, 4, 5(P),,, ,,,8, 9 (For detail refer to 5-3)
-
0(P)=Valid, 1=invalid
-
-30, -29, -28,,, ,,, 49, 50
(For detail refer to 6-1-3)
-30, -29, -28,,, ,,, 49, 50
(For detail refer to 6-1-3)
-30, -29, -28,,, ,,, 49, 50
(For detail refer to 6-1-3)
5, 6, 7,,, 12(P),,, 30 (For detail refer to 9-5)
3(P), 4, 5, 10, 20, 50
(For detail refer to 11-4-2)
-
5(P), 10, 20, 50 (For detail refer to 11-1-1)
5(P), 10, 20, 50 (For detail refer to 11-1-1)
5(P), 10, 20, 50 (For detail refer to 11-1-1)
-
-
-20, -19, -18,,, ,,, 29, 30 (For detail refer to 4-8-4)
-20, -19, -18,,, ,,, 29, 30 (For detail refer to 4-8-4)
-
-
-
2WAY SYSTEM

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents