Outdoor Unit Control Panel Led Display - Panasonic U-8ME1E8E Service Manual

2way system
Table of Contents

Advertisement

2. Outdoor Unit Control Panel LED Display

LED (RED)
1
2
(Both ON)
(OFF)
(ON)
(Both OFF)
(Blinking alternately)
(Both blinking)
(Blinking alternately)
6
After the power is turned ON (and automatic address setting is not in progress), no communication
with the indoor units in that system is possible.
After power is turned ON (and automatic address setting is not in progress), one or more indoor
units are confi rmed in that system; however, the number of indoor units does not match the number
that was set.
Automatic address setting was completed successfully. (After the power is turned ON, and
automatic address setting is not in progress, the number of detected indoor units connected to that
system matches the number that was set, and regular communications are occurring.)
Automatic address setting is in progress.
At time of automatic address setting, the number of indoor units did not match the number that was
set.
Alarm display
LED 1 blinks M times, then LED 2 blinks N times. The cycle then repeats.
M = 2: P alarm 3: H alarm 4: E alarm 5: F alarm 6: L alarm
N = Alarm No.
Example: LED 1 blinks 2 times, then LED 2 blinks 17 times. The cycle then repeats.
Alarm is "P17."
(
: ON
Display meaning
6 - 4
2WAY SYSTEM
Trouble Diagnosis
: Blinking
: OFF)

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents